Back Panel
PA-3060 Back Panel
Figure 4 shows the back panel of the PA-3060 firewall and Table 4 describes the back-panel
features.
Figure 4. PA-3060 Back Panel
Table 4. PA-3060 Back-Panel Features
Item
Description
Power supplies
Two redundant, hot-swappable power supplies.
Grounding lug
To ground the system, use a grounding wire of at least 14 American
Wire Gauge (AWG). Attach the 14 AWG wire to an agency-
approved crimp connector (Tyco 34120 or certified Lug), crimped
with the proper crimping tool and attached to the protective
grounding lug. Use a size #8-32 nut and a star washer (supplied) to
secure the grounding lug to the chassis and connect he other end to
the building ground. Toque the nut to 15 in-lbs. Do not over tighten.
Exhaust fans
Four exhaust fans that provide front-to-back ventilation and cooling
for the device.
Power Supplies
Grounding Lug
Exhaust Fans