ACR

 air curtains 

Operation and Maintenance Documentation

10.

   OPERATION AND MAINTENANCE

The engine and fan of the ACR air curtains are maintenance-free devices but regular check-ups are advised, especially motor and 

bearing (fan’s rotor should rotate freely, free from any axial and radial throws/run-outs and undesired knocks/rattles. 

The heat exchanger requires systematical cleaning of all dirts /impurities off. Before the start of the heating period, the heat exchanger 

is advised to be cleaned with compressed air directed to the air outlets; there is no need for dismantling of the device. 

Pay special attention when cleaning the exchanger’s fin due to high possibility of damaging them. If the fin is bent use a special tool. If 

the device has not been used for a longer period of time, unplug it before the next use.

The heat exchanger is not equipped with any fire protection device. The heat exchanger may be damaged if the room temperature

goes below 0°C; anti-freeze liquid must be added to the water circulation/system. Anti-freeze liquid must be appropriate for the

material the exchanger is made of (copper) as well as other elements of the hydraulic system/circulation. The liquid must be diluted

with water accordingly to the manufacturer’s recommendation.

NOTICE !

•  Any and all repair and maintenance works must be conducted with the power off and the heat 

input disconnected.

•  Only  suitably  qualified  staff  well  acquainted  with  the  safety  regulations  concerning  handling 

with an electrical device must be employed when the device is being installed, started and op

-

erated

•  In the event of coolant leak, when the water system is under pressure, any repairs of the leak

-

age are strictly prohibited.

•  Any repairs of the device must be conducted only if the device is disconnected from the power 

supply.

•  If the device being operated gives metallic clatter, vibration or the level of noise is increasing, 

check if the

•  mounting of the fan has not become loose – in case of any problems contact the installer of the 

device or the

•  PAKOLE TRADE Kft. Authorized Service immediately.

 

11.

   TROUBLESHOOTING AND TECHNICAL PROBLEMS

Possible problems and solutions are shown below. To eliminate a problem encountered contact the PAKOLE TRADE Kft. Authorized 

Service.

Fault, symptoms

Potential causes

Solutions

No heating, fan not operating

No power supply

Check the power switch Check the

power supply Check the power cable – if it is dam-

aged - replace the cable

Damage to the fan

Replace the motor

Damage to the switches on control panel

Check the switches – if are damaged – replace

Heating medium leakage

• 

leakage on joints with hot water supply system

• 

leakage in collector

Loss of tightness

Sealing supply system; repairing the heat exchanger

Heat output drop

Temperature of the heating medium differs 

from the required one Contaminated heat 

exchanger’s surface

Restore the temperature of the heating medium 

Clean the surface of the heat exchanger

Содержание ACR 100W

Страница 1: ...EN Operation and Maintenance Documentation www pakole com 008_039_011_190902__V001_en Type ACR 100W ACR 100E ACR 100C ACR 150W ACR 150E ACR 150C ACR 200W ACR 200E ACR 200C AIR CURTAINS...

Страница 2: ...100 150 200 W water heater and C 11 without heater to the COMFORT panel 11 Diagram of connecting two ACR 100 150 200 W water heater and C without heater to one COMFORT panel 11 Diagram of connection o...

Страница 3: ...air curtain is connected directly to the cable please make sure there is a splitter protecting against any undesired discon necting Pay special attention while transporting the device not to damage t...

Страница 4: ...ting cold air from entering the heated space In summer the curtains may be used as cooling devices preventing the entry of hot air and pollutants from outside The ACR air curtains are designed to prot...

Страница 5: ...pirals Large heat exchange surface surface of contact of the heat exchanger with heated air Fully automatic heat control depending on air flow Complete elimination of the risk of system overheating du...

Страница 6: ...ol panel With larger door openings it is possible to mount more curtains of the same type one by one to create an uninterrupted air flow The curtain is permanently mounted in either a horizontal or ve...

Страница 7: ...the wall in a horizontal position using 2 mounting brackets to the horizontal system In the brackets there are 9mm holes for M8 screws In the EPP housing drill holes 12 13mm in front of existing hole...

Страница 8: ...g drill holes 12 13mm in front of existing holes in the steel in take grille The exact location is indicated by special tags on the EPP housing and the figure below Then insert the spacer sleeves into...

Страница 9: ...er use a vent which is located on the exchanger collector on the engine side ATTENTION It is necessary to ensure that the unit is properly leveled When it is mounted in a position other than vertical...

Страница 10: ...L not supported function in this settings the device does not work To install the control panel unscrew the screw remove the front cover and panel board fix the panel to the wall and replace the panel...

Страница 11: ...not include power cord or main switch Diagram of connecting one ACR 100 150 200 W water heater and C without heater to the COMFORT panel Power supply 230V 50Hz Security system B4 Cross section of pow...

Страница 12: ...E B25 Control Panel COMFORT 3 speed fan control with thermostat OMY 5x 1 0mm In the MASTER curtain between the L1 NC terminal replace the factory made fuse C 3 15 with C 6 3 400V 50Hz power supply wir...

Страница 13: ...circuit between terminal 3 on Comfort Panel and Terminal 2 in the ACR curtain The on off switch itself should be installed in a place suitable for the curtain user Warning The Comfort Panel thermostat...

Страница 14: ...ated PP OPERATION Digital signal 1 potential free contact closed information about the operation of the curtain reed relay on door opened Digital signal 0 potential free contact opened Reed relay off...

Страница 15: ...he COMFORT panel in ON position READY FOR OPERATION 1 signal activated PP OPERATION Digital signal 1 potential free contact closed information about the operation of the curtain reed relay on door ope...

Страница 16: ...16 ACR air curtains Operation and Maintenance Documentation 9 DIMENSIONS OF THE ACR 100 150 200 W E C CURTAINS...

Страница 17: ...at input disconnected Only suitably qualified staff well acquainted with the safety regulations concerning handling with an electrical device must be employed when the device is being installed starte...

Страница 18: ...authorized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case of accidentally happened or directly caused mi...

Страница 19: ......

Страница 20: ...PAKOLE TRADE Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 www https www pakole com E mail mail pakole hu Tel 36 22 316 484 Fax 36 22 316 074 www pakole com...

Отзывы: