11
MidiHeat EHA
MA45-32E
ENGLISH
Figure 5
3~ 220–240V
Output
Fuses F1-4
min. cable area
2x9 = 18kW
32A
6 mm
2
2x12 = 24kW
50A
10 mm
2
2x15 = 30kW
50A
10 mm
2
3x12 = 36kW
50A
10 mm
2
3x15 = 45kW
50A
10 mm
2
4x15 = 60kW
50A
10 mm
2
White
Pink
Blue
Blue
White Pink
Heating element connected for 220-240V 3-phase
3~ 380–415V
Output
Fuses F1-4
min. cable area
2x9 = 18kW
20A
2,5 mm
2
2x12 = 24kW
25A
4 mm
2
2x15 = 30kW
32A
6 mm
2
3x12 = 36kW
25A
4 mm
2
3x15 = 45kW
32A
6 mm
2
4x15 = 60kW
32A
6 mm
2
4x18 = 72kW
32A
6 mm
2
White
Pink
Blue
Blue
White
Pink
Heating element connected for 380-415V 3-phase
Figure 4
Figure 3
NOTE!
Reconnection from 400V to 230V
On delivery, the heater is marked with a name plate and connected for 400V 3-phase (see figure 4) but can be reconnected for
230V 3-phase.
The input cabling to the contactors should then be fused according to the table above, see figure 5 + electrical drawing.
NOTE! If reconnection is performed, the supplied alternative rating plate must be fitted.
The input cabling for the contactors (K1A-K4A) shall be connected according to the electrical drawing in the way shown in figure
3 below.
NOTE! It is important that the screwdriver has the correct dimensions, and is pushed into the correct hole in
the correct way.