
pH/chlorine regulator AUTODOS 5000 - 2005-01-21
Eng_Autodos5000.doc ver 3.2 - page 18
2.13.6. Channel Specific Set-up (Combined Chlorine)
Press the buttons ’
SET VALUE’
+ ’
SELECT FUNCTION’
for the combined chlorine channel and you will enter
the combined chlorine channel set-up, indicated by the text ’SEt CCL’ and flashing LED’s ’OFF’ and ’AUTO’ on
the combined chlorine channel. To exit the set-up, press ’
CAL’
or step out from the last row. The following
alterations may be made in channel specific set-up (Combined Chlorine):
Row
Text
Setting
Explanation
-01
dos
oFF/ono/FrE/Cur
Dosing type – no dosing/on-off/frequency/current output
-02
P
0.10-2.00
P-band
-03
d
000-100
D-time
-04
dF
010-180
Max. dosing frequency, strokes/min
-05
Ldt
000-060 (min)
Long dosing time alarm, 0 = no alarm function
-06
oFt
000-600 (sec)
Min. time OFF for relay, 0 = no function (on-off)
-07
ont
000-600 (sec)
Min. time ON for relay, 0 = no function (on-off)
-08
Cur
--0/--4
Current output 0-20mA/4-20mA
-09
C-L
0.00-9.99
Value for 0/4mA
-10
C-H
0.00-9.99
Value for 20mA
The row is altered by pressing the '
↓
' or '
↑
' button below display 2. While the '
↓
' or '
↑
' button is pressed, display 3
shows the present row number and display 2 shows the selected set-up type (ex. ’CCL’ ’-01’). When the buttons are
released, display 2 shows a descriptional text and display 3 shows an editable numerical value or a text. The set-up
options are edited by pressing the '
↓
' or '
↑
' button below display 3, with numeric values you decrease/increase the
value and with text information you switch between alternatives.
2.13.7. Channel Specific Set-up (pH- Acid/Alkali)
Press the buttons ’
SET VALUE’
+ ’
SELECT FUNCTION’
for the pH channel and you will enter the pH channel
set-up, indicated by the text ’SEt ACi’ or ’SEt bAS’ and flashing LED’s ’OFF’ and ’AUTO’ on the pH channel. To
exit the set-up, press ’
CAL’
or step out from the last row. The following alterations may be made in channel specific
set-up (pH):
Row
Text
Setting
Explanation
-01
dos
oFF/ono/FrE/Cur
Dosing type – no dosing/on-off/frequency/current output
-02
P
0.10-2.00
P-band
-03
d
000-100
D-time
-04
dF
010-180
Max. dosing frequency, strokes/min
-05
Ldt
000-060 (min)
Long dosing time alarm, 0 = no alarm function
-06
oFt
000-600 (sec)
Min. time OFF for relay, 0 = no function (on-off)
-07
ont
000-600 (sec)
Min. time ON for relay, 0 = no function (on-off)
-08
Cur
--0/--4
Current output 0-20mA/4-20mA
-09
C-L
0.00-9.99
Value for 0/4mA
-10
C-H
0.00-9.99
Value for 20mA
The row is altered by pressing the '
↓
' or '
↑
' button below display 2. While the '
↓
' or '
↑
' button is pressed, display 3
shows the present row number and display 2 shows the selected set-up type (ex. ’ACi’ ’-01’). When the buttons are
released, display 2 shows a descriptional text and display 3 shows an editable numerical value or a text. The set-up
options are edited by pressing the '
↓
' or '
↑
' button below display 3, with numeric values you decrease/increase the
value and with text information you switch between alternatives.