8
4.1
Commissioning
Danger
• All electrical connections must be carried out by an authorized installer and in accordance with local rules
and regulations.
Before initial operation, check the following:
• Electrical connection has been properly completed.
• Protective earth has been connected.
• Safety devices in place (protection grid).
• Leftover installation materials and foreign materials have been removed from the casing.
Testing the installation:
• Adjustment may be required in the electrical compartment during test (i.e. changing of the potentiometer), however
during operation the lid must be closed.
When putting into operation, check the following:
• Connection data corresponds to the specifications on the nameplate: Maximum v6%, -10%, according to IEC
38. Rated current must not be exceeded with more than 5% at rated voltage.
• The direction of rotation should correspond to direction-of-rotation arrow (3 phase).
• Smoothness of motor operation, (no abnormal noises).
Sound levels exceeding 70 dB(A) may occur depending on size (see www.pacificventilation.com for detailed
information).
5
Maintenance
5.1
Important
Danger
• Make sure that the mains power supply to the unit is disconnected before performing any maintenance
or electrical work!
• Fan impeller has come to a complete standstill.
• Should the supply cable be damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard
• The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use
protective clothing.
• Do not lift the fans by the connecting cable, connection box, motor bracket, impeller or inlet cone.
269415 | A001