AFX SERIES® OPERATION MANUAL
SECTION 5: UNPACKING AND INSTALLATION
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 81 of 485
5.16
AFX Cabinet Systems Turn ON and Turn OFF Procedures
AFX Cabinet systems can be turned on or off using the front panel mounted circuit breakers
on the master and auxiliary units. Turn On and Turn Off sequence recommendations are
listed below and illustrated in Figure 5-20. The sequence is not critical as long as units are
turned on within 15 seconds of each other. If more time elapses, an error may be displayed
and the master/aux discovery process should be restarted from the PARALLEL UNITS screen
in the SYSTEM menu. Refer to section 6.8.7, “PARALLEL UNITS Screen”.
Alternatively, the master grid power disconnect switch that is required for cabinet
installation can be used to connect or disconnect all units from grid power at the same time.
5.16.1
Cabinet Power Turn ON using Circuit Breakers
The following turn on sequence is recommended:
1.
Turn
ON
bottom auxiliary unit
first
by pulling its front panel circuit lever to the
upward (ON) position.
2.
Turn
ON
any additional auxiliary units between the bottom auxiliary unit and the
top Master unit by pulling each front panel circuit lever to the upward (ON) position.
3.
Turn
ON
the Master unit
last
by pulling its front panel circuit lever to the upward
(ON) position.
This will ensure all auxiliary units are up and will be found when the master starts the
discovery process.
5.16.2
Cabinet Power Turn OFF using Circuit Breakers
The turn off procedures is the reverse of the turn on one as follows:
1.
First, turn
OFF
AFX System output using the OUTPUT button on the Master unit
front panel first to make sure any load is powered down first.
2.
Then, turn
OFF
the Master unit
first
by flipping its front panel circuit lever to the
down (OFF) position.
3.
Turn
OFF
the first auxiliary unit located below the master unit by flipping the front
panel circuit lever to the down (OFF) position.
4.
Turn
OFF
the bottom auxiliary unit
last
by flipping its front panel circuit lever to the
down (OFF) position.
Note:
Turning off all AFX units in a cabinet DOES NOT remove MAINS power from it. If any
service is to be performed on the cabinet, make sure the MAINS power (grid power)
is disconnected first.
Содержание AFX Series
Страница 484: ......