background image

8

SCAVENGE (AIR PURGING).

During the operation with minimum power output, the controller will activate flue sca-

venge (purging) to ensure removal of accumulated gases. Scavenge (purging) is

provided with temporary fan operation in higher speed.

EXTINCTION (SHUT DOWN).

When in this mode the controller turns off the fuel auger and engages the fan to en-

sure complete fuel combustion and the burner cool down. Fan power when in

EXTINCTION (SHUT DOWN) mode is determined by the technician. When

EXTINCTION (SHUT DOWN) is finished the controller is switched into CLEANING,

STAND-BY or STOP mode, provided EXTINCTION (SHUT DOWN) followed as a re-

sult of STOP button pressing.

BLANKING MODE.

In this mode, the controller changes the fan speed on the value programmed by

a service technician to burn off excess fuel and cool the burner. After putting out the

fire controller switches to CLEANING, ARMED or STOP depending on what caused

the start of the sequence Afterburning EXTINCTION.

CLEANING.

Automatic burner cleaning occurs after time set limit by programmer. In this mode

controller starts cleaning system for preset time. After this procedure controller

resets back to STANDBY mode.

AUGER (MANUAL) REFILLING.

User may activate auger manual refilling function. When device is in STOP mode,

press START and hold button for 5 seconds to start refilling. Refilling follows accor-

ding to the time programmed by the technician or until it is manually turned off with

STOP button.

AUGER EXTINCTION (EMERGENCY SHUT DOWN).

If the auger is equipped with a temperature sensor, a temperature increase above

the range programmed by the technician, it will result in activation of auger ignition

alarm. The controller turns off the fan and auger. If the burner is equipped with the

stoker, the device is switched additionally into AUGER EXTINCTION(EMERGENCY

SHUT DOWN) mode. During shut down the stoker is engaged for the time needed to

remove the ignited fuel from the stoker. In addition if the burner has cleaning mecha-

nism, the controller will activate the cleaning cycle and remove fuel from the burner.

Содержание RK-2006SPGMS

Страница 1: ...OPERATION MANUAL RK 2006SPGMS Pellet fuel burner fitted boiler temperature controller Version 8B28 version of the adapter MZK MZM2...

Страница 2: ......

Страница 3: ...er The temperature sensor should be placed in metering locations that shall be dry Figure 2 presents the electrical connection diagram CAUTION Before plugging in the controller first check if the wiri...

Страница 4: ...of the device is to set the preset boiler temperature In this hands U need to turn the boiler thermostat knob 4 to set the correct value and confirm it with the OK button or press the knob CAUTION If...

Страница 5: ...ty indicator the higher the capacity the brighter the flame 10 Cleaning device work indicator 11 Stoker work indicator 12 Feeder temperature 13 The operation indicator summer mode 14 The temperature c...

Страница 6: ...water pumps operation but automatic ignition does not follow AUGER EXTINCT EMERGENCY SHUT DOWN Fuel ignition in auger channel The controller empties ignited fuel from the auger channel until temperatu...

Страница 7: ...feeding rate is adjusted by the technician Pressing STOP button exceeding time limit for cleaning thermostat contacts opening or if water temperature in domestic water tank is obtained during operati...

Страница 8: ...uence Afterburning EXTINCTION CLEANING Automatic burner cleaning occurs after time set limit by programmer In this mode controller starts cleaning system for preset time After this procedure controlle...

Страница 9: ...sensor Activation of the alarm will result in fan and auger turning off and switching the controller into STAND BY mode CAUTION This alarm does not result in engagement of inner sound system and does...

Страница 10: ...Damage to the outside temperature sensor In the event of damage to the external temperature sensor controller causes alarm the minimum temperature is maintained in the circuits dependent the outside t...

Страница 11: ...rature 1 9 Measured return water temperature 1 10 Temperature of the burner PT 1000 CT 1 2 1 11 1 12 Ignitor turn off depending on the temperature 200 C 500 C 1 13 Current furnace brightness FD 1 1 14...

Страница 12: ...hot water without priority option central heating and domestic water pumps operation follow at the same timee 1 7 Bacterial flora liquidation in domestic water tank the controller enables manual activ...

Страница 13: ...n burner work Parameters described below refer to counters that accumulate information on opera tion of the burner since its first start It is not possible to cancel counter readings 1 15 Burner work...

Страница 14: ...arameters service mode Service parameters are divided into groups For each group are assigned service parameters possible to change Entry into service mode after press and hold for about 3 seconds the...

Страница 15: ...uel feed 0s 250s F 4 3 Fuel feed cycle 1s 250s F 4 4 Fuel feed during ignition 0 100 F 4 5 Fuel feed for max burner power 1 100 F 4 6 Fuel feed for min burner power 1 100 F 4 7 Stoker work mode see de...

Страница 16: ...Thermostat 9 1 Boiler minimum temperature 30 C 69 C F 9 2 Boiler maximum temperatur 70 C 90 C F 9 3 Boiler upper hysteresis 1 C 20 C F 9 4 Boiler power switching hysteresis 1 C 9 C F 9 5 Boiler prote...

Страница 17: ...le to test various output devices This feature is available in service mode only if the adju stment process is stopped ie The regulator before entering the service mode was in STOP mode Selecting outp...

Страница 18: ...the controller offers the function of scavenge air purging which simply includes periodical switching on of the fan during burner operation for the purpose of removal of accumulated gases 3 11 Fan sca...

Страница 19: ...e lighter In this case Initial Fuel Dose set ting be shall be programmed as the value over 0s 4 5 Fuel feed for max burner power this parameter specifies fuel dose fed to the burner during operation w...

Страница 20: ...selected in Auger ignition test setting and contacts of X input shall be closed 4 13 Auger ignition temperature this parameter specifies auger temperature when the controller activates auger ignition...

Страница 21: ...time after igniter and fan are switched on the controller tests temperature increase or brightness in the selected location of the burner If flame is not detected within the time programmed in this pa...

Страница 22: ...attached to the time set in parameter Cleaning mechanism work time After turning off the regulator output deducts the time set in parameter Cleaning mecha nism retraction time and the time set in par...

Страница 23: ...e is tur ned on accordingly less often depending on the SECOND MECHANISM K DIVISOR parameter If K is 2 the bottom drawer is turned on at every second move of the top drawer AUTO ASH REMOVAL In other c...

Страница 24: ...ired number of shut downs Setting the parameter to 0h control the minimum time off work without cleaning 6 9 The maximum working time without cleaning this parameter is available on ly when the cleani...

Страница 25: ...domestic water path handling Election of MIXING PUMP setting will switch domestic water in the circuit purposed for control of the mixing pump In this case return water temperature sensor shall be co...

Страница 26: ...burner due to excee ding the hysteresis top of the boiler This parameter specifies how long is needed to stabilize the system after the hot water tank with priority enabled During the stabili zation c...

Страница 27: ...parameter specifies hysteresis parameter of boiler limit temperatures switching off 9 6 Boiler overheating temperature this parameter specifies boiler water temperature when the controller switches of...

Страница 28: ...ate adaptive algorithm preset boiler temperature Value should be selected empirically according to the characteristics of the controlled object If you are working adaptive algorithm and frequently cha...

Страница 29: ...no parity bits 2 bits of silence default setting 10 5 MODBUS access level defines to what extent the configuration of parameters is available to the ModBus protocol NONE no parameters are provided by...

Страница 30: ...ump AUTO Continuous pump operation 13 3 Weather control This function allows you to attach a weather control 13 4 Temperature set point circuit the temperature is maintained behind the mixing valve 13...

Страница 31: ...d ensure the system as well uses the main circuit as the central heating circula tion when the 2 circuit operates 13 14 Use the main thermostat when the parameter is set to YES the standard boiler the...

Страница 32: ...e depends mainly on the outside temperature and thermal properties of a building The controller enables the user to set the adequate inclination and shift of the weather charcteristics The relations b...

Страница 33: ...ther characteristics will be changed 8 Controller disassembly If controller disassembly is necessary follow the following procedure Disconnect the boiler and controller from power supply Remove the co...

Страница 34: ...34 Figure RK 2006SPGMS Controller connection diagram...

Страница 35: ...treated as household waste The appliance shall be handed over to the applicable collection point for used up electrical and electronic equipment for recycling purpose Ultimate disposal of the applianc...

Страница 36: ...Manufacturer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: