Adjusting the pump pressure
-
Remove the pressure gauge plug from the filter cover.
-
Use an external pressure gauge.
-
Start the indirect air heater.
-
Allow the motor to reach full speed.
-
Adjust the pressure (using a flat screwdriver):
-
Turn the pressure relief valve clockwise to increase pressure.
-
Turn the pressure relief valve anti-clockwise to decrease pressure.
For indirect air heater model ZF50, the correct pump pressure is 6 PSI.
-
Stop the indirect air heater – Remove the pressure gauge and replace the plug.
Note: Always use only original spare parts.