17
8.
CONNECTION OF THE UNIT
Mains supply, control panel cable and, if necessary, comfort function connector should be connected
to the Unit, according to the following diagram:
Figure 6. Connection of the Unit
IMPORTANT!
Number and purpose of connections depends on device configuration:
*1 – if internal preheater is not present
*2 – if option selected prior ordering the Unit
*3 – if option selected prior ordering the Unit
IT IS PROHIBITED
to connect any cables or devices to the connectors of the control panel and comfort
functions, despite similarity to any standard connectors. External similarity of connectors does not
guarantee compatibility – connected devices may fail or damage the Unit. Failure of the Unit due to
incompatible supplementary parts connection will void the warranty!
IT IS PROHIBITED
to connect or disconnect control panel or WiFi controller without turning off the
mains power first. The failure of the control panel or the Unit due to improper connection will void
the warranty!
- control panel or WiFi controller connector (USB)
- comfort functions connector (RJ-45)
- Mains cable (230V, 3x1.5mm
2
L+N+PE)
- el. preheater cable (*1) (230V, 3x1.5mm
2
L+N+PE)
- el. damper actuator (*3) connector
- el. heater cable (*2) (230V, 3x1.5mm
2
L+N+PE)