PLANNED MAINTENANCE
DESCRIPTION
FREQUENCY
IN CHARGE
OPERATING INSTRUCTION
Photocell cleaning and verification of all safety
features
Monthly
User
Clean with a damp cloth and test the safety
features
Control of gate hinges and supports, gate
balancing
As required
User
Check the condition of the welds and corrosion.
Disengage the motor and check the balance and
any friction points of the sash.
Electronic clutch sensitivity control (torque
adjustment) of the control unit
Semiannual
Electrician
Check the torque setting as indicated in EN 12453 -
EN 12445.
Protection degree control
Semiannual
Electrician
Check that there are no traces of moisture or water
inside the electrical enclosures.
Leakage current control
Annual
Electrician
Check that it is 7.5A lower
Check the tightening of the bolts of the articulated
arm. Checking the connection to the motor
Semiannual
User
Check that the bolts are tightened well and that the
arm has no abnormal play. Check the coupling with
the motor.
Signage control
Semiannual
User
Check that it is complete and intact
EMERGENCY RELEASE
Remove cap A, insert the supplied key B into hole C, turn the key (left or right) until you
hear the first click.