Praktika T-02(K) turnstile
20
AP and STOP inputs operate only in a potential mode, i.e. as long as
the input is closed on GND contact the turnstile operates in the
corresponding mode. After contacts opening - turnstile switches to the
"Stop" mode irrespective to the mode of operated that was used before
ACS operation.
LEFT and RIGHT inputs can operate both in the potential and in
pulse mode (responding upon GND contact closure). Pulse mode is set on
default.
In order to switch to a potential mode set J1 jumper (Fig. 8). In this case
the mode of left / right passage turns on only during the control signal to
LEFT / RIGHT inputs. Mode of free passage can be set by control signals
to both inputs simultaneously. Priorities of LEFT and RIGHT inputs at the
switch to the pulse mode remain unchanged.
Motherboard contains two relay outputs for ACS operating on the
principle of "dry contacts» - Pass Okl and Pass Ok2. NO and COMM -
normally open connection, NC and COMM - normally closed connection.
Activation of one of the contact sets suggests the passage in the
corresponding direction (PassOk1 - right, PassOk2 - left). "Dry contact"
closes / opens when arms rotate at an angle of 60 degrees and return to the
starting position when passage is completed.
Motherboard contains relay output for ACS operating on the principle of
"dry contacts» - Status. NO and COMM - normally open connection, its
contacts close when the turnstile switches to "AP" and D3 LED indicator
lights up.
Also the motherboard contains the following LED indicators:
Содержание Praktika T-02
Страница 1: ...Installation guidelines www oxgard com info oxgard com Tel 7 812 366 15 94 Praktika T 02 К turnstile ...
Страница 2: ......
Страница 7: ...Installation guidelines 7 Fig 1 General view of turnstile Dimensions are shown on Fig 2 ...
Страница 22: ...Praktika T 02 K turnstile 22 Fig 9 Numbering of RC panel buttons ...
Страница 39: ...Installation guidelines 39 ...