5

PART 3 – TAKE READINGS, cont.

Press  

   so that the ZOOM 2 is set to 

‘850nm’

.

Press  

  so that the Dual OWL is set to 

‘850nm’

.  The left-hand indicator LED will be lit.

Record the 850nm reading for the current fiber under test then disconnect the patch cables from both ends of the patch 
panel and move to the next port on the patch panel.

Repeat  

  and  

  for each fiber in the cable under test until all fibers have been tested at 850nm.

For testing 1300nm, again connect to the first fiber under test, except this time use the mandrel-wrapped patch cable 
connected to the 1300nm port.

Press  

   so that the ZOOM 2 is set to 

‘1300nm’

, and press  

  so that the Dual OWL is set to 

‘1300nm’

.  The right-

hand indicator LED will be lit.

Record the 1300nm reading for the current fiber under test.

Disconnect the patch cables from both ends of the patch panel and move to the next port on the patch panel.

Repeat  

   and  

  for each fiber in the cable under test until all fibers have been tested at 1300nm.

(end of procedure)

QUICK REFERENCE GUIDES

Optical Power Meter:

ZOOM 2

Fiber Optic Light Source: DUAL OWL Series 

PAGE 5 OF 5

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

FIGURE 6

Taking

Readings

dBm

2.00

-

850

nm

SC connectors shown here;
connector style may vary

 

 LIGHT SOURCE

CONNECTOR PORTS

Do NOT insert APC connector
into either light source port 

Содержание ZOOM 2 Series

Страница 1: ...WL N9623 West US Hwy 12 Whitewater WI 53190 Phone 262 473 0643 Internet OWL INC COM Revision 1 5 July 19 2011 Optical Wavelength Laboratories OWL ZOOM 2 Series Test Kits Optical Loss Testing Quick Reference Guide For part numbers KIT Z2 D2xx KIT Z2 D285xx KIT Z2 D2xx L2xx KIT Z2 D285xx L213xx ...

Страница 2: ...ing orreferencingofpowerlevels 4 determiningthecorrectlinkbudgettopassorfailby Completeunderstandingofeachoftheseissuesiscriticalforperformingproperfiberoptictests GETTINGSTARTED Thank you for your purchase of this OWL optical loss test kit Included in this kit is a ZOOM 2 optical power meterandaDualOWLseriesmultimodefiberopticlightsource BEFOREYOUTEST Priortoperformingacertificationtest therearea...

Страница 3: ... PART2 setareferenceforthewavelength s usedduringfiberlinkmeasurement and PART3 takemeasurements EQUIPMENTPORTS Figure2showstheportsusedduringthisprocedure Theseportsmayvarydependinguponthemodelofequipment REQUIREDACCESSORIES ensuretestcableshavethepropercoresizeandconnectortype multimode reference cables must be wrapped and secured around a mandrel as required by national and internationalFiberOp...

Страница 4: ...tch cable should be replaced if it is belowtheacceptablepowerlevel Onceproperoperationhasbeenverified removethestraightpatchcablefrombothunitsandsetitaside continue procedure on next page UNITS ZERO FIGURE 3 Straight Patch Cable Connection 2 QUICK REFERENCE GUIDES Optical Power Meter ZOOM 2 Fiber Optic Light Source DUAL OWL Series PAGE 2 OF 5 SC connectors shown here connector style may vary LIGHT...

Страница 5: ...d if it is below the acceptable power level Once proper operation has been verified leave the mandrel wrapped patch cable connectedtothepowermeterandlightsource thencontinueontothenextstep PART2 SETREFERENCE Settingareferenceiscommonlyreferredtoas zeroing Ensure the power meter and light source are still connected together Figure 4 then press and hold ontheZOOM2tosetthereferencefor850nm The ZOOM 2...

Страница 6: ...s that the meter and light sourcehavebeensuccessfully zeroed at1300nm PART3 TAKEREADINGS Disconnect the mandrel wrapped patch cable from the detector port on the ZOOM 2 then bring both units to the opposite endsofthelinkundertest RemembertobringthestraightpatchcablewiththeZOOM2 ConnecttheZOOM2andthe850nmportontheDualOWLtothelinkundertest Figure6 UNITS ZERO QUICK REFERENCE GUIDES Optical Power Mete...

Страница 7: ...300nmport Press so that the ZOOM 2 is set to 1300nm and press so that the Dual OWLis set to 1300nm The right handindicatorLEDwillbelit Recordthe1300nmreadingforthecurrentfiberundertest Disconnectthepatchcablesfrombothendsofthepatchpanelandmovetothenextportonthepatchpanel Repeat and foreachfiberinthecableundertestuntilallfibershavebeentestedat1300nm end of procedure QUICK REFERENCE GUIDES Optical P...

Отзывы: