1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
FIGURE 3
Taking
Readings
dB
2.00
-
1310
nm
SET REFERENCE
STEP 11
Press and hold the
8
/AUTO
button on the WaveTester to set it into AUTO mode.
The WaveTester display should change to show readings in ‘
dB
’.
STEP 12
Press and hold the
8
/AUTO
button on the WaveSource until you see the indicator LED begin flashing,
then immediately release the button.
The right-hand indicator LED on the WaveSource will begin alternating between the colors
and
, which
indicates that the output wavelengths are automatically switching.
The WaveTester will automatically sense the wavelength switching, and will co-ordinate with the WaveSource.
STEP 13
Press and hold the
UNITS/ZERO
button on the WaveTester to set the reference for both wavelengths
simultaneously.
NOTE:
After the references have been set, do NOT press the
8
/AUTO
button on either the WaveTester or the
WaveSource. Doing so will take the units out of AUTO mode.
TAKE READINGS
STEP 14
Remove the patch cable from the detector port on the WaveTester, and bring both units to the opposite
ends of the link under test.
STEP 15
Connect the WaveTester and WaveSource to the link under test as shown in Figure 3 below.
STEP 16
Press
<SAVE>
on the WaveTester to store readings
for both 1310nm and 1550nm simultaneously for
the current fiber under test.
STEP 17
Disconnect the patch cables from both ends of the patch panel and move to the next port on the patch
panel.
STEP 18
Repeat steps 16 and 17 for each fiber in the cable under test until all fibers have been tested.
red
green
LIGHT SOURCE CONNECTOR
PORT NOTES:
– CONNECTOR TYPE MAY VARY
– DO NOT INSERT ANGLED
PHYSICAL CONTACT (APC)
CONNECTOR