RUN LINK WIZARD, cont.

STEP 22

Connect the Fiber OWL 4 BOLT to your fiber link as shown in Figure 3.

Press 

<F1>

 to continue.

STEP 23

Review the end-to-end fiber length.  In the example screenshot at right, the end-to-

end fiber length could be within the range of 1000 to 1006 meters.

Press 

<F2>

 to continue.

STEP 24

The end-to-end length shown here is the length that will be entered into the Link 

Wizard configuration.

OPTIONAL:

 you may also enter the fiber length manually.

Press 

<DONE>

 to continue.

NOTE:

 Length testing is complete.  You may now remove all of the patch cables from the link under test.

STEP 25

Enter the number of connections (i.e. patch panels) in the link under test.  Typical fiber 

networks will have 2 connections – one for a patch panel located at each end of the link.  

Press 

<DONE>

 to continue.

STEP 26

Enter the number of splices in the link under test.   Splices can be either fusion or 

mechanical.  Typical singlemode networks will have zero splices.

NOTE:

 some connectors use mechanical splice technology for termination.  If the link under 

test is terminated with these “no-polish, no-epoxy” type connectors, they should be considered 
as mechanical splices.

Press 

<DONE> 

to continue.

STEP 27

Review your Link Wizard setup.  

If correct, press 

<F1>

 and continue on to the next step.

If changes need to be made, press 

<F3>

 and go back to STEP 17.

STEP 28

Press 

<F1>

 until the asterisk (

*

) is in front of 1310nm (as shown at right).  

Press 

<F2>

 to begin the SET REFERENCE procedure for 1310nm.

STEP 29

Connect the detector

 

port on the meter and 1310nm light source (right-hand port) 

together with a singlemode cable as shown in Figure 2 (on the reverse side of this page).

Press 

<F1>

 to continue.

FIBER A

FIBER B

PATCH FIBER A TO

DONE

END OF THE LINK

^

CONNECT

^

_____________________

FIBER B AT THE FAR

(FIBER PAIR REQUIRED)

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

FIGURE 3

Fiber OWL 4 BOLT

Length Test Connection

FIBER LENGTH

01000 -0/+6 meters

TEST

DONE

INDEX

1310nm Index(n)=1 490

_____________________

(A CONNECTION IS WHEN
TWO FIBER CONNECTORS

MATE

USUALLY A PATCH

<---

--->

SHIFT

PANEL)

[2 ]

INLINE CONNECTIONS?

_____________________

SPLICES IN THE FIBER
BEING TESTED:

<---

--->

SHIFT

[0 ]

ENTER THE NUMBER OF

_____________________

01000 Meters
02 Connections

00 Splices

YES

NO

INDOOR SingleMode

IS THIS CORRECT?

TIA-568B 3/CAN-T529

_____________________

Standard 

»

Length 

»

Connections 

»

Splices 

»

Fiber Type 

»

WAVELEN REF dBm

TYP

---------------------

*1310nm NOT SET (-10)

WAVE

SET

DONE

1550nm NOT SET (-10)

SET SOURCE REFERENCES

_____________________

1310nm

DONE

SOURCE

CONNECT

_____________________

 LIGHT SOURCE CONNECTOR 

PORT NOTES:

– CONNECTOR TYPE MAY VARY
– DO NOT INSERT ANGLED 

PHYSICAL CONTACT (APC) 
CONNECTOR

[1 TO 65535]

<---

UNITS

--->

[01000] METERS

ENTER FIBER LENGTH:

_____________________

Содержание 4 BOLT Series

Страница 1: ...262 473 0643 Internet OWL INC COM Revision 1 1 25909 Fiber OWL 4 BOLT Series Test Kits Certification Testing Quick Reference Guide For part numbers KIT FO4B WSSDst KIT FO4B WSSDsc Optical Wavelength Laboratories e C s i h o W i c e e h i T n O s p e i t r i c o a t l a r F o i b b e a r L T h e t s g t n E e l q e u v i p a m W e l n a t c i t p O OWL ...

Страница 2: ...il by Complete understanding of each of these issues is critical for performing proper fiber optic tests GETTING STARTED Thank you for your purchase of this OWL certification test kit Included in this kit is a Fiber OWL 4 BOLT optical power meter and a WaveSource multimode fiber optic light source This quick reference guide will assist you in setting up your test kit for a standards based certific...

Страница 3: ...ORT button to switch to the SM PORT The indicator LED on the right hand side should be 1310nm STEP 3 Power on the Fiber OWL 4 BOLT STEP 4 From the OPERATING MODE menu select SIMPLE METER STEP 5 Press F3 until the Fiber OWL 4 BOLT is set to 1310nm wavelength STEP 6 The power reading on the Fiber OWL 4 BOLT display should be approximately 10 00 dBm If the reading is 12 00 dBm or below it is recommen...

Страница 4: ...twork under test Press F2 to select the fiber type STEP 21 Press 1 to use measure the fiber length with the Fiber OWL 4 BOLT It is important to set the current date in order to ensure that the correct date appears on the certification report XXXXXXXXXXXXXXXXXXXXX X X XXXXXX 1 LINK WIZARD X X XXXX 2 TAKE READINGS XXXXXXXXXXXXXXXXXXXXX X X XXXXXXXX 3 MAIN MENU XXXXXXXXXXXXXXXXXXXXX XXXXX X XXXXXX ST...

Страница 5: ...t together with a singlemode cable as shown in Figure 2 on the reverse side of this page Press F1 to continue FIBER A FIBER B X XXXXXXX X PATCH FIBER A TO X X X XXXXX DONEXXXXXXXXXXXXXXXXX END OF THE LINK X X X XXXXXX xxxx XX XX XXXX CONNECT _____________________ FIBER B AT THE FAR X X X X XXX FIBER PAIR REQUIRED X X 1 2 3 4 5 6 7 8 9 10 1112 1 2 3 4 5 6 7 8 9 10 1112 FIGURE 3 Fiber OWL 4 BOLT Len...

Страница 6: ...to opposite ends of the link STEP 37 Connect the units to the first fiber to test as shown in Figure 4 Your readings will vary from the example below STEP 38 Once the STORE button becomes active press F2 to store the data point If this is the first fiber in the link you may be prompted to enter a new label STEP 39 Press F3 to save the data point STEP 40 Disconnect the patch cables from the patch p...

Отзывы: