oventrop Aktor M ST/2P L Скачать руководство пользователя страница 8

Commissioning 

Electromotive actuator 24 V

8

115801384-V01.01.2020

(3)

Setting of the travel direction with a control volt

-

age of 10 V DC
Travel direction and 
position feedback 
100...0 %

Travel direction and 
position feedback  
0....100 %

(4)

Equal percentage char-
acteristic line

Linear characteristic 
line

(5)

When switching switch 5, the current position 
of the stem will be saved as emergency end 

position.

(6)

When switching switch 6, the stored data for 
valve adaptation will be deleted and a new ini

-

tialisation run will be triggered.

6.2  Connection of the power supply

NOTICE

Damage to the actuator due to operation 

in unmounted state

The actuator can be damaged and its func-

tion be impaired when operating the actuator 
electrically without valve.

 

f

The actuator must only be connected to 

the power supply after installation. 

NOTICE

Damage to the control technology due to a 

high peak load when switching the actua-

tor on 

 

f

Use switching components which are 

designed for a short-term peak load of up 
to 12 A. 

Make sure that the connecting cables are 
disconnected from the power supply before 

installing the connecting cables.

 

f

Carry out the assignment (see Illust. 5).

 

f

Connect the power supply.

After having connected the power supply, the 
internal energy store will be charged first. This 

process takes about 3.5 minutes.

Charging of the energy store generally has 
priority over the actuator functions.

 

Z

After having charged the internal energy store, the 
actuator will carry out an initialisation run. The ac

-

tuator will move to the upper end position first and 
then to the lower end position.

 

The product will be ready for operation after initiali

-

sation.

 

Z

Protect the stroke position indicator by turning the 

dust cover (position (2) in Illust. 2) around by 180°.

6.2.1  Steady control

1 2 3 4 5

24 V AC/DC

0 V AC/DC

Y = 0/2..10 V DC  

0 V DC

U = 0..10 V DC 

BN

GY

YE

GN

BU

Illust. 5:  Pin assignment for steady control

(1)

0 V AC/DC

blue (BU)

(2)

24 V AC/DC

brown (BN)

(3)

Y = 0/2..10 V DC

grey (GY)

(4)

Position feedback 0 

V DC

yellow (YE)

(5)

Position feedback 

 

0..10 V DC

green (GN)

6.2.2  2 point control

2 3

24 V AC/DC

0 V AC/DC

1

BN

GY

BU

Illust. 6:  Pin assignment for 2 point control

(1)

0 V AC/DC

blue (BU)

(2)

24 V AC/DC

brown (BN)

(3)

0 V or 24V AC/DC  

grey (GY)

Содержание Aktor M ST/2P L

Страница 1: ...Valves controls system Operating instructions EN Electromotive actuator 24 V Aktor M ST 2P L 0 10V ...

Страница 2: ......

Страница 3: ...sonnel qualification 5 2 3 2 Risk of burns due to hot components and surfaces 5 2 3 3 Availability of the operating instructions 5 3 Technical description 6 3 1 Construction 6 3 2 Functional description 6 3 3 Technical data 6 4 Transport and storage 7 5 Installation 7 5 1 Initial installation 7 6 Commissioning 7 6 1 Configuration of the DIP switches 7 6 2 Connection of the power supply 8 6 2 1 Ste...

Страница 4: ...required Enumeration 1 2 Fixed order Steps 1 to X Z Result of action 2 Safety related information 2 1 Correct use Safety in operation is only guaranteed if the product is used correctly The actuator may be used in indoor heating ventila tion and air conditioning systems Any other use of the product will be considered incorrect use Claims of any kind against the manufacturer and or his authorised r...

Страница 5: ... legal regulations qualified tradespeople are able to carry out any work on the described product professional ly User The user has to be informed by the qualified trades people as to the operation 2 3 2 Risk of burns due to hot components and surfaces f Allow the product to cool down before working on it f Wear suitable protective clothing to avoid unprotect ed contact with hot system components ...

Страница 6: ...closed Connection Fixed pre assembled cable 1 5 m 5 x 0 5 mm2 Motor deactiva tion Drive stem extending load dependent retracting load dependent Display LED display for operating volt age and status Travel noise 28 dB A during normal operation Piston stroke Max 10 mm Floating time 22 s mm Emergency float ing time 5 s mm Operating power 500 N Position indicator Stroke scale Emergency con trol functi...

Страница 7: ...o the connection thread of the adapter 3 Hand tighten the collar nut Avoid cross threading NOTICE Damage to the actuator when tightening the collar nut with excessive torque The actuator can be damaged and its func tion be impaired if the collar nut is over tight ened f Hand tighten the collar nut 6 Commissioning 6 1 Configuration of the DIP switches f Remove the casing cover f Configure the DIP s...

Страница 8: ...ke sure that the connecting cables are disconnected from the power supply before installing the connecting cables f Carry out the assignment see Illust 5 f Connect the power supply After having connected the power supply the internal energy store will be charged first This process takes about 3 5 minutes Charging of the energy store generally has priority over the actuator functions Z After having...

Страница 9: ...ontact with hot components may lead to burns f Allow the product to cool down before working on it NOTICE It may not be possible to unscrew the col lar nut by hand In some circumstances the actuator closes the valve with the maximum actuating power of 500 N In this case the collar nut can no longer be unscrewed by hand f Do not use pliers or similar to loosen the collar nut f Move the actuator to ...

Страница 10: ...itch 6 see Illust 4 Z The actuator is ready for operation 11 Disposal Guideline 2012 19 EU WEEE Waste electrical and electronic equipment WEEE must not be disposed of with do mestic waste but must be dropped off at a collection point for the recycling of electri cal and electronic appliances NOTICE Risk of environmental pollution Incorrect disposal for instance with the domestic waste may lead to ...

Страница 11: ......

Страница 12: ...OVENTROP GmbH Co KG Paul Oventrop Straße 1 59939 Olsberg GERMANY www oventrop com 115801384 V01 01 2020 ...

Отзывы: