E--883--4N--E

10

6. INTERNAL COMPONENTS AND FUNCTIONS

6.1 Front Panel
6.1.1 Display

The display is a 128 X 128-dot multiple function display capable of showing the data, units of measure, 

error messages, and other information at the same time. (The display is backlighted.)

6.1.2 On-Screen Menu Items

The units of measurement vary with configuration. Their selection is made in the SET mode. Available 

menu items are:

(1) Uncorrected total flow (TOTAL COUNT)

Incoming flow pulses are calibrated for meter error, integrated before correction for temperature, 

and the obtained totalized flow is indicated. Resolution, or the minimum unit of measurement, which 

varies with customer specifications, is set up with front-panel keys. This unit automatically becomes 

identical with the output pulse unit. 

While the total flow is retained irrespective of power cycling, it is resettable to zero following a power 

cycle if so configured in the SYS mode.

(2) Corrected total flow (TOTAL COUNT(C))

The reading calibrated for meter error and temperature is integrated. Other specifications remain 

the same as (1).

(3) Uncorrected instant flowrate (FLOW RATE)

The instant flowrate calibrated for meter error is indicated before temperature correction.

(4) Corrected Instant flowrate (FLOW RATE(C))

The instant flowrate calibrated for meter error and corrected for temperature is indicated. 

(5) Temperature (TEMPERATURE)

The temperature value currently fed to the instrument is indicated. If a problem arises in the course 

of temperature conversion, such as out-of-scale, a default fallback value is indicated. 

(6) Meter error correction factor (METER ERROR)

Meter  error  correction  factor  corresponding  to  the  flowrate  currently  fed  to  the  instrument  is 

indicated. 

Based on this reading, the total before correction is calibrated for meter error.

         

[Indicated reading] = 1 + 

−−−

(7) Temperature correction factor (TEMP. COMPEN.)

The  temperature  correction  factor  calculated  based  on  the  temperature  currently  fed  to  the 

instrument is indicated. The corrected total flow is compensated based on this reading.

(See Section 7.2 "Implementation of Temperature Correction".)

NOTE: For more information about menu items and options, see "KEY OPERATION MANUAL".

6.1.3 Error Messages

When  an  erratic  condition  arises,  an  error  message  automatically  appears  on  the  display.  (The 

information represented by error messages are listed on page 15.)

If  two  or  more  concurrent  errors  are  involved,  individual  messages  will  be  scrolled  at  intervals  of 

approximately 3 seconds. When an error condition disappears, an error message automatically goes out 

and the normal display is resumed.

NOTE: An error logging function can store a maximum of 20 events each of which consists of year, 

month,  day,  hour  and  minutes  of  error  occurrence  and  recovery.  (Complete  details  are 

covered in the Key Operation Manual.)

E

100

Содержание EL4131

Страница 1: ...nowledge contained in this manual you can expect the best possible results over a long service life of this instrument Keep this manual for ready reference It is suggested that the instruction manuals...

Страница 2: ...NTERNAL COMPONENTS AND FUNCTIONS 10 6 1 Front Panel 10 6 1 1 Display 10 6 1 2 On Screen Menu Items 10 6 1 3 Error Messages 10 6 1 4 Front Panel Keypad 11 7 CALCULATION FORMULAS 12 7 1 Implementation o...

Страница 3: ...1 170 9 EL4501 175 10 DIP SWITCH CONFIGURATION 182 Model with communication capabilities COMMUNICATION MANUAL Ins No E 880CM E CONTENTS 1 COMMUNICATION CAPABILITY OVERVIEW 5 2 NETWORK CONFIGURATION 5...

Страница 4: ...ire supply complete informa tion as to the product name model number product number ratings and other pertinent information 1 2 Transportation Precautions 1 In order to safeguard against damage during...

Страница 5: ...the companion flowmeter is simple by keystrokes on the front panel keypad or by inserting an IC card into the slot 2 Built around a microprocessor the instrument carries out calculations entirely in d...

Страница 6: ...ed to install instruments alongside each other dimensions in Fig 3 2 are suggested 3 Recommended mounting height is given in Fig 3 3 3 2 3 Installation 1 Front mount the instrument through the cutout...

Страница 7: ...s are found on the back of the instrument Fig 4 1 4 3 Description of Terminal Blocks for External Connections Terminal blocks for external connections TB1 TB2 and TB3 are found on the back of the inst...

Страница 8: ...4 to 20mADC 1 to 5VDC 5 Temp in b Pt100 3 wire 5 6 B 6 Pulse out 1 No Polarity Uncorrected total flow Static relay 7 A 7 8 4 to 20mADC 1 to 5VDC 8 Pulse out 2 No polarity Corrected total flow Static r...

Страница 9: ...Same as output pulse unit m3 etc Display capacity 8 digits Corrected total flow Same as output pulse unit m3 C etc Uncorr instant flowrate m3 h etc Corr instant flowrate m3 h C etc Temperature To the...

Страница 10: ...nd corrected for temperature is indicated 5 Temperature TEMPERATURE The temperature value currently fed to the instrument is indicated If a problem arises in the course of temperature conversion such...

Страница 11: ...ion keys Four round keys Mainly used for function selection such as activating the input conditions selected and recon figuration Shift keys Four triangular keys Used for moving the cursor moving betw...

Страница 12: ...ont panel keys and the frequency pulse information flowrate 7 2 Implementation of Temperature Correction Corrected total flow Q2 Q1 K K a b t0 t c t0 t 2 where Q2 Total flow corrected for temperature...

Страница 13: ...ems of the total mass flow and total calorific flow and make sure that incoming pulses are being accumulated Also verify that pulse output and analog output are properly generated 5 Remove the simulat...

Страница 14: ...ure correction factor 1 Temperature reading correct 1 A fault in internal assembly While fluid is allowed to flow Fails to count pulses fails to produce a pulse output 1 Input signal line correctly wi...

Страница 15: ...e range check 12 A D CONVERT ERROR A D converter circuit error 13 DENSITY CONVERT ERROR Density converter circuit error 14 TEMP 1 PT OVER Temperature Pt input 1 overflow 15 TENP 1 PT UNDER Temperature...

Страница 16: ...D Converter Press Input Ckt analog Temp Input Ckt analog Temp Input Ckt Pt Analog Output Circuit Pulse Output Circuit 1 Pulse Output Circuit 2 Pulse Output Circuit 3 Multi plexer Isolation Test Pins...

Страница 17: ...e N Non Output item 2 Pulse output 2 B 1 Before correction pulse width 1ms B 5 Before correction pulse width 50ms B 9 Before correction special pulse width C 1 After correction pulse width 1ms C 5 Aft...

Страница 18: ...am Japanese D W E Wiring diagram English D A J Compression coef cient calculation process Japanese D A E Compression coef cient calculation process English D T J Inspection procedure Japanese D T E In...

Отзывы: