27
ROOM ABOVE (non-insulated ceiling)
ATTIC ABOVE (insulated ceiling)
B
A
Ceilng firestop from
bottom
Ceiling firestop from
top
Note:
Use same dimensional lumber for framing
ceiling firestop and joists.
Figure 8.5 Installing the Ceiling Firestop
• Install a ceiling firestop whenever chimney penetrates
ceiling/floor.
• Mark and cut an opening in ceiling as shown in
Figure 8.5.
• Frame the opening with the same size lumber used in
the ceiling joists.
• Nail the ceiling firestop to the bottom of the ceiling joists
when there is a room above.
• Use an attic insulation shield if the ceiling is insulated.
The ceiling firestop may then be attached above or below
the joists.
D. Install Ceiling Firestops
CAUTION! Risk of Fire!
Ceiling firestops must be used
whenever the chimney penetrates a ceiling/floor.
• Chase construction requires ceiling firestops at each
floor or every 10 ft (3.05 m) of clear space.
• The ceiling firestop slows spread of fire and reduces cold
air infiltration.
WARNING!
Risk of Fire! DO NOT seal area between
firestop opening and chimney pipe except where they
enter the attic or leave the warm air envelope of the
home (use 600° F sealant).
Outdoor Lifestyles by Hearth & Home Technologies Inc.• 4072-137 Rev F • 11/25/13
Catalog #
A
B
Angle
in.
mm
in.
mm
FS338
14-1/2
368
14-1/2
368
0°
FS339
14-1/2
368
18-3/8
467
15°
FS340
14-1/2
368
23
584
30°