IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

The OutBack FLEXware PV-8 and PV-12 Combiners are listed by ETL as PV Combiners under the follow-

ing standards:

•  UL 67, 11th Edition

•  UL 1741, First Edition

•  CSA  C22.2, No.29-M1989

These enclosures meet Type 3R rainproof requirements when mounted vertically or leaning back to 14 
degrees (3/12 pitch).

This enclosure is rated for up to 150VDC circuit breakers and up to 600VDC fuses. 

Grounding Instructions 

– Each enclosure should be connected to a grounded, permanent wiring 

system. For most installations, the negative battery conductor should be bonded to the grounding 

system at one (and only one) point in the DC system. All installations must comply with all national 

and local codes and ordinances. System grounding as required by the National Electric Code, ANSI 
/NFPA 70-1996, or other appropriate codes is the responsibility of the system installer.

The equipment ground on FLEXware PV Combiner is marked with this symbol:   

NOTE

: Solar panels produce electrical current when light is present, even during overcast 

weather. Do not wire from the array to the PV-8 or the PV-12 Combiner. Complete all 
connections inside the combiner fi rst and then connect at the array.

OutBack Power Systems’ FLEXware

FLEXware is a convenient system of all-aluminum, powder-coated modular enclosures with associated 

mounting hardware and stainless steel fasteners for housing OutBack power components. Our 

indoor-rated enclosures and mounting plates off er secure and centralized installations for various 

combinations of FX Series Inverter/Chargers, OutBack Charge Controllers, the OutBack HUB, MATE, and 

Auto-Transformer, as well as breakers, bus bars, and balance-of-system components. 

General Wiring and Installation Instructions

•   Remove any necessary knockouts before securing the combiner to its mounting surface.

•   Mount the combiner, securing it appropriately.*

•   Slide the circuit breakers or fuse holders onto the DIN rail and lock in place.

•   Secure the box lugs to the Combiner Bus Bar. 

•   Install the Combiner Bus Bar and secure it to either the fuse holders or the circuit breakers.

•  Connect all wires to the fuse holders or circuit breakers and the box lugs, securing them 

  according to the listed torque values.
•  Connect the wires to the solar array.

*FLEXware PV-8 and PV-12 Combiners are designed for weather-resistant outdoor installation when appropriate 

fasteners and secure mounting surfaces are used. The back of each combiner has knockouts 

 

to accommodate 

fasteners, U-bolts, or other hardware for secure attachment to a solid surface, including pole mounting. Both the 

surface and the fastening hardware must be suffi

  cient to support the weight of the combiner.

Содержание FLEXware PV 12

Страница 1: ...PV 8 Combiner PV 12 Combiner User s Guide Includes Mounting and Installation Instructions T M...

Страница 2: ...2...

Страница 3: ...sclaimer UNLESS SPECIFICALLY AGREED TO IN WRITING OUTBACK POWER SYSTEMS a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS...

Страница 4: ...mple Circuit Breakers 11 Wiring Diagram 12 FLEXware PV 8 Combiner Wiring Sample Fuses 13 Wiring Diagram 13 Fuse Holder Installation 14 FWPV 12 Combiner Features 16 Sample FW CBUS 12 Bus Bar Installati...

Страница 5: ...ir warranties The customer must return the component s to OutBack securely packaged properly addressed and shipping paid We recommend insuring your package when shipping Packages that are not securely...

Страница 6: ...re FLEXware is a convenient system of all aluminum powder coated modular enclosures with associated mounting hardware and stainless steel fasteners for housing OutBack power components Our indoor rate...

Страница 7: ...UE AWG mm2 in lbs Nm 14 10 2 1 5 3 20 2 3 8 8 4 25 2 8 6 13 3 21 2 35 4 0 Torque Data for Box Lug WIRE SIZE TORQUE AWG mm2 in lbs Nm 14 10 2 1 5 3 35 4 0 8 8 4 40 4 5 6 4 13 3 21 2 45 5 1 2 0 3 13 3 2...

Страница 8: ...6...

Страница 9: ...ockout punchable to 1 5 Can be mounted on a 3 4 or 6 pole Roof mountable at an angle down to 3 in 12 pitch 140 NOTE A combiner can use either circuit breakers or fuses depending on the installation re...

Страница 10: ...8 Circuit breaker installation using included bus bar hardware Fuse holder installation Bus bar hardware installed Optional DIN Rail End Clamp FW EC DIN Sample FW CBUS 8 Bus Bar Installations...

Страница 11: ...or six input strings Eight DIN mount OBB circuit breakers Electrical knockouts capable of accommodating copper wire sizes from 2 0 to 14 AWG 67 4 mm2 to 2 08 mm2 Ground Bus Bar Negative Terminal Bus B...

Страница 12: ...10 Knockouts and Dimensions FWPV 8 Combiner Front View Knockouts for 3 4 and 6 U bolts pole mount installation Knockouts for fl at surface installation Front View Side View Bottom View...

Страница 13: ...ck Charge Controller s lugs can accept cable sizes ranging from 2 0 to 14 AWG 67 4 mm2 to 2 08 mm2 copper wires FLEXware PV 8 Combiner Wiring Sample Circuit Breakers Individual PV circuit breakers up...

Страница 14: ...UAL 2 0 AWG OUTPUT WIRES TO CHARGE CONTROLLER OR INVERTER POSITIVE COMBINATION BUS BREAKERS PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV GROUNDING EL...

Страница 15: ...67 4 mm2 to 2 08 mm2 copper wires Ground Bus Bar DIN rail Dead front Individual array wiring enters through the bottom knockouts to stay weather resistant Back chassis knockout Individual PV array fu...

Страница 16: ...BUS UP TO DUAL 2 0 AWG OUTPUT WIRES TO CHARGE CONTROLLER OR INVERTER PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV POSITIVE COMBINATION BUS FUSEHOLDERS WITH FUSES GROUNDING E...

Страница 17: ...15...

Страница 18: ...unchable to 2 EKO 1 back knockout punchable to 1 5 Can be mounted on a 6 or 8 pole Roof mountable at an angle down to 3 in 12 pitch 140 NOTE A combiner can use either circuit breakers or fuses dependi...

Страница 19: ...17 Sample FW CBUS 12 Bus Bar Installations Fuse holder installation using included bus bar hardware Circuit breaker installation Optional DIN Rail End Clamps FW EC DIN Bus bar hardware installed...

Страница 20: ...for eight input strings 12 DIN mount OBB circuit breakers Electrical knockouts capable of accommodating copper wire sizes from 2 0 to 14 AWG 67 4 mm2 to 2 08 mm2 Combiner shown with optional fuse hold...

Страница 21: ...19 Bottom View Knockouts for 6 and 8 U bolts used in pole mount installation Knockouts and Dimensions Knockouts for flat surface installation Side View Front View FWPV 12 Combiner...

Страница 22: ...the DIN rail and installed flush against the dead front mounting flange Individual PV circuit breakers up to 15 amp 150 VDC are available from OutBack Dead front DIN rail COMB iner Bus Bars combine al...

Страница 23: ...TO DUAL 2 0 AWG OUTPUT WIRES PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV POSITIVE COMBINATION BUS P...

Страница 24: ...nockouts to stay weather resistant Dead front mounting flange Ground Bus Bars Back chassis knockout Fuse holders must be secured to the DIN rail and in stalled flush against the dead front mounting fl...

Страница 25: ...ER TO CHARGE CONTROLLER OR INVERTER UP TO DUAL 2 0 AWG OUTPUT WIRES PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV PV POSITIVE COMBINATION BUS POSITIVE CO...

Страница 26: ...nteractive AC Coupled Backup Mobile Please circle installed components FLEXware Enclosures and Mounting Components IOB Kits The system is equipped with circle one FW X240 PSX 240 PSX 240 Relay Please...

Страница 27: ...25...

Страница 28: ...European Sales Office Barcelona ESPA A 34 600 843 845 19009 62nd Avenue NE Arlington WA 98223 USA 1 360 435 6030 www outbackpower com 900 0003 01 00 REV A...

Отзывы: