Radian Dimensions (includes MATE3):

85 cm (29.1") tall X 60.6 cm (23.9") wide

5.

Secure the inverter to the surface using a minimum 
of 1 wall screw (or other appropriate hardware). 

6.

Follow the instructions for installing the GS Load Center.

7.

Follow the instructions for installing the bracket for the MATE3.

8.

Follow appropriate instructions for installing the PV array and grid-tied 
inverter (if not already present). 

Wire Sizes & Torque

Mounting

WARNING:  Fire/Explosion Hazard

Do not place combustible or flammable materials within 3.7 m (12 feet) of the equipment.  This unit employs mechanical 
relays and is not ignition-protected.  Fumes or spills from flammable materials could be ignited by sparks.

WARNING:  Personal Injury

Use safe lifting techniques and standard safety equipment when working with this equipment.

IMPORTANT:  

Clearance and access requirements may vary by location.  Maintaining a 91.4 cm (36") clear space in front of the system for 
access is recommended.  

Consult local electric code to confirm clearance and access requirements for the specific location.

900-0156-01-00 Rev B.vsd\Page-2\2013-06-14

©2013 OutBack Power Technologies.  All Rights Reserved.

Torque Requirements

Circuit Breaker Stud

Torque

M8

¼ - 20

5/16 - 18

3/8 - 16

AC Wire Sizes and Torque Values

It is recommended that conductors be 16 mm

2

THHN copper, or larger, rated to 75°C 

(minimum) unless local code requires otherwise.

AWG

In-lb

#14 - 10

#8

#6 - 4

#3

#2

#1

1/0

Wire Size

Torque

Radian Mounting:

1.

Ensure the mounting surface is strong enough to handle 3 times the total weight of 
all the components.  Add a piece of plywood if necessary to strengthen the surface.

2.

Attach the wall bracket to the surface centering the mounting holes on the sides 
with the wall studs.  Use all 6 mounting screws to secure the bracket.

3.

Lift the inverter so that the inverter bracket is above the wall bracket.

4.

Lower the inverter into place so that the inverter bracket slips into the wall bracket.  

1

3

4

6

GSLC175-AC-230

N
E
U

L1 L2

GRID

L1 L2

GEN

N
E
U

N
E
U

L1 L2

OUT

RELAY

AUX

+  -
12V 
AUX

Switch

INV

Remote

Battery 

Temp

Minimum DC Cable based on the 

DC Circuit Breaker Amperage

Torque

DC 

Circuit 

Breaker

Cable Size

125

70 mm

2

(1/0)

175

70 mm

2

(2/0)

250

120 mm

2

(4/0)

80

25 mm

(#4 AWG) 

60

16 mm

(#6 AWG)

MATE3

GS8048

GSLC

1

2

2

3

4

5

7

8

8

9

ON/OFF

INV

9

Plywood 

(Optional)

Wall Board

Wall 

Bracket

Wall Stud

Side View

Inverter 
Bracket

40.6 cm (16")

Plywood (Optional)

Wall Board

Wall Stud

Wall Bracket

Wall Stud

1

2

2

3

4

5

5

6

7

8

8

10

11

12

13

14

15

16

17

Radian Series

Inverter/Charger

MATE3 

Mounting 

Bracket

MATE3 

GS Load Center

7

Shunt

Bolt 3/8"

Lock Washer

Flat Washer

Battery 

Negative (–) 

Lug

Negative Battery Cable 

Connections 

DC Plates

3/8 - 16

Upper holes (+)

3/8 - 16

Lower holes (+)

3/8 - 16

Shunt Bolts (–)

Lower holes (+)

CAUTION:  Equipment Damage 

When connecting cables from the inverter to the battery 
terminals, ensure the proper polarity is observed.  
Connecting the cables incorrectly can damage or 
destroy the equipment and void the product warranty.

!

PV and Grid-Tied 

Inverter

mm

2

2.5 – 6

10

16 – 25

35

35

50

70

Nm

20

25

35

35

40

50

50

2.3

2.8

4.0

4.0

4.5

5.6

5.6

Nm

5.6

25.4

25.4

4.0

4.0

In-lb

50

225

225

35

35

In-lb

20

35

50

225

225

60

225

225

225

60

50

Nm

2.3

4.0

5.6

25.4

25.4

6.8

25.4

25.4

25.4

6.8

5.6

Battery 

Negative (–) 

Lug

Control Wiring Terminal Block:

The 12V AUX and RELAY AUX terminals are used to 
control the devices which disconnect the grid-tied 
inverter (the ROCB and the relays).  These devices can 
also automatically start a generator if one is present.

AC Circuit Breakers

1
2
3
4

DC Terminals - Inverter

AC Terminals - Inverter

5

DC Circuit Breakers

6
7

8

Mechanical Interlock 

(Bypass)

9

10

Communication Ports
Auxiliary Terminals

11
12
13
14
15

AC OUT Bus Bar L1

16
17

GRID IN Bus Bar L1
GEN IN Bus Bar L1
AC Neutral
Ground
DC Positive (+) Plate
DC Negative (–) Bus Bar

Remote Operated 

Circuit Breaker (ROCB)
Relays

Grid-Tied Inverter 

Bus Bar

Bolt 3/8"

DC Positive (+) 

Plate

Battery 

Positive (+) 

Lug

Flat Washer

Positive Battery Cable 

Connections 

Nut

Lock Washer

Flat Washer

15

6