Available From:
19009 62nd Avenue NE, Arlington, WA 98223
Phone: 360-435-6030 Fax: 360-435-6019 www.outbackpower.com
The MATE2M is a complete management tool for your OutBack marine power conversion system. The onboard
CPU coordinates the operation of all your OutBack system components for maximum performance and smooth
system integration.
A backlit LCD provides a display for system monitoring while four soft keys allow navigation of the menu system and
adjustment of settings. Information for up to 10 inverter/chargers and other OutBack power conversion equipment
is available at your fingertips through the communications HUB. Your programmed settings are stored in permanent
memory to eliminate the need
to reprogram the system in the event of a system shutdown or battery replacement.
The OutBack MATE2M includes a built in clock and calendar which allows timer based programming of power system operation. This enables
the user to specify a generator’s run time to a specific time period of the day or week.
“Corrosion resistant aluminum marine PS2 system
components are available for larger applications.”
MATE2M Specifications
Operation
4 soft keys, dedicated inverter and AC input keys
Input
OutBack Cat5e RJ45 network cable
Output (RS232 model only)
RS232 serial to PC communication for data logging (optional software required)
Display
Back lit 4 line LCD
System Monitoring
AC/DC Voltage and Current Meters, Errors and Warnings
Adjustable Parameters
Shore Cord Amperage, Generator Start/Stop
Settings Memory
32k nonvolatile flash RAM
Dimensions HxWxD
4.5 x 6.15 x 1.7” (11 x 16 x 4 cm)
Weight
1 lbs (454 g)
Warranty
2 Year Standard / 5 Year Optional
M-Series Specifications
Sealed Models
Vented Models
FX2012MT
FX2524MT
FX2532MT
VFX2812M
VFX3524M
VFX3232M
Nominal DC Input Voltage
12 VDC
24 VDC
32 VDC
12 VDC
24 VDC
32 VDC
Continuous Power Rating at 25° C
2000 VA
2500 VA
2500 VA
2800 VA
3500 VA
3200 VA
AC Voltage/Frequency
120 VAC 60 Hz
120 VAC 60 Hz
120 VAC 60 Hz
120 VAC 60 Hz
120 VAC 60 Hz
120 VAC 60 Hz
Continuous AC RMS Output at 25° C
17.0 amps AC
20.8 amps AC
20.8 amps AC
23.3 amps AC
29.2 amps AC
26.6 amps AC
Idle Power
Full
≈ 20 Watts
≈ 20 Watts
≈ 21 Watts
≈ 20 Watts
≈ 20 Watts
≈ 21 Watts
Search
2.6 Watts
2.6 Watts
2.6 Watts
2.6 Watts
2.6 Watts
2.6 Watts
Typical Efficiency
90%
92%
92%
90%
92%
92%
Total Harmonic Distortion
Typical
2%
2%
2%
2%
2%
2%
Maximum
5%
5%
5%
5%
5%
5%
Output Voltage Regulation
± 2%
± 2%
± 2%
± 2%
± 2%
± 2%
Maximum Output Current
Peak
56 amps AC
70 amps AC
56 amps AC
56 amps AC
70 amps AC
56 amps AC
RMS
40 amps AC
50 amps AC
40 amps AC
40 amps AC
50 amps AC
40 amps AC
AC Overload Capability
Surge
4800 VA
6000 VA
4800 VA
4800 VA
6000 VA
4800 VA
5 Second
4000 VA
4800 VA
4000 VA
4000 VA
5000 VA
4000 VA
30 Minutes
2500 VA
3200 VA
2500 VA
3200 VA
4000 VA
4000 VA
AC Input Current Maximum
30 amps AC
30 amps AC
30 amps AC
30 amps AC
30 amps AC
30 amps AC
AC Input Voltage Range (MATE Adjustable)
80 to 150 VAC
80 to 150 VAC
80 to 150 VAC
80 to 150 VAC
80 to 150 VAC
80 to 150 VAC
AC Input Frequency Range
54.0 to 66.0 Hz
54.0 to 66.0 Hz
54.0 to 66.0 Hz
54.0 to 66.0 Hz
54.0 to 66.0 Hz
54.0 to 66.0 Hz
DC Input Range
10.5 to 17.0 VDC
21.0 to 34.0 VDC
28.0 to 45.3 VDC
10.5 to 17.0 VDC
21.0 to 34.0 VDC
28.0 to 45.3 VDC
Continuous Battery Charge Output
80 amps DC
55 amps DC
35 amps DC
125 amps DC
85 amps DC
45 amps DC
Minimum Recommended DC Breaker
OBDC-250
OBDC-175
OBDC-125
OBDC-250
OBDC-250
OBDC-175
Recommended Battery Cable
#4/0 AWG
#2/0 AWG
#2/0 AWG
#4/0 AWG
#4/0 AWG
#2/0 AWG
Recommended Battery Types
Flooded lead acid, AGM, gel
Flooded lead acid, AGM, gel
Warranty
Standard 2 year / Optional 5 year
Standard 2 year / Optional 5 year
Certifications
ETL listed to UL458
ETL listed to UL458
Weight
Unit
56 lbs (25 kg)
54 lbs (25 kg)
Shipping
67 lbs (30 kg)
62.2 lbs (28 kg)
Dimensions (H x W x L)
Unit
13 x 8.25 x 16.25” (33 x 21 x 41 cm)
12 x 8.25 x 16.25” (30 x 21 x 41 cm)
Shipping
21.75 x 13 x 22” (55 x 33 x 56 cm)