INSTALLATION GUIDE
16.4.2021
VC02-0072
145 A
135 A
1000 V
VC02-0075
145 A
135 A
1000 V
VC02-0076
145 A
135 A
1000 V
Type
Screw
Screw 1
M10
Tightening torque
1,5-6 mm² (M6)
2 Nm
Stripping length
L
16 mm
SW
5
2,5-16 mm² (M10)
3 Nm
Screw 2
M6
25-50 mm² (M10)
8 Nm
SW
3
-
-
Max. Wire cross section
50 mm²
1,5 mm
2
2,5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
35 mm
2
50 mm
2
-
3
3
3
3 (1)
2 (1)
1 (1)
(1)
70 mm
2
95 mm
2
120 mm
2
150 mm
2
185 mm
2
240 mm
2
300 mm
2
400 mm
2
-
-
-
-
-
-
-
-
Ouneva Oy
Teollisuustie 21
Tel. +358 400 179 750
www.ounevagroup.fi
FI-82730 Tuupovaara, Finland
www.ounevaproducts.fi
Product information
Product code
Product name
I
n Al
I
n Cu
U
n
Pole branching connector Al 2x50 / Cu 2x35 + 1,5-6 mm² Grey
Pole branching connector Al 2x50 / Cu 2x35 + 1,5-6 mm² Blue
Pole branching connector Al 2x50 / Cu 2x35 + 1,5-6 mm² Ye/Gr
Installation
On cable
Connection
Sealing (Optional, OD01-0078 sealing plug kit needed)
Cross section and max. number of copper conductors / space (aluminium conductors in parenthesis)
3-8 Nm
(M10)
L
SW
The specified max. amount of conductors
refers only to industrially installed
terminals.
Installation
Connector can be used for both
copper- or
aluminium
conductors. It's recommended to
use anti-corrosion paste for aluminium
conductors. (e.g. Penetrox).
It is allowed to use max. three adjacent cross
sectioned conductors per space (Copper
conductors). The nominal max. cross section
value must not be exceeded.
It is allowed to install only one aluminium
conductor per space.
Using ferrule is recommended for fine-stranded
conductors.
Sector shaped conductors must be pre-rounded
before installation.
Support connector during tightening the screws.
2 Nm (M6)
LED input
Open the housing with for
example flat-bladed
screwdriver
Close with light press after
connection
Note!
IP33 protection class is
achieved with a sealing
kit OD01-0078. Without
sealing kit with ≥25
mm
2
cables in main
inputs (
1
) and 6 mm
2
in
LED inputs (
2
)
protection class is IP23.
2
1
Cut holes to sealing plugs and
pull conductors trough (with 2,5
- 16 mm
2
conductors excl. LED
input).
Install the conductors into
dedicated inputs as mentioned
above.
Use intact sealing plugs to
fulfill empty connector inputs
by pressing sealing plug
properly tight. Plug goes inside
as described in picture right.