background image

INSTALLATION GUIDE

Product code

I

n Al

I

n Cu

U

n

290 A

320

690 V

I

max Al

I

max Cu

U

max

-

-

-

Type

Screw head for tool

SW

6 mm

Conductors

Tightening torque M

25-50 mm²

14 Nm

Stripping length

L

1

27±1 mm

70-150 mm²

30 Nm

 

-

-

-

-

1,5 mm

2

2,5 mm

2

6 mm

2

10 mm

2

16 mm

2

25 mm

2

35 mm

2

50 mm

2

-

-

-

-

-

3(1)

3(1)

3(1)

70 mm

2

95 mm

2

120 mm

2

150 mm

2

185 mm

2

240 mm

2

300 mm

2

400 mm

2

2(1)

1(1)

1(1)

1(1)

-

-

-

-

Ouneva Oy

Teollisuustie 21
FI-82730 Tuupovaara

Tel. +358 400 179 750

www.ounevagroup.fi

Finland

[email protected]

www.ounevaproducts.fi

 

Product data

Product name

VC02-0013

Universal connector 25-150mm²

Installation

Screw M16

Wiring, pcs / connection, Cu(Al) 

Connection

1xAl/Cu 25-150 mm²

L

1

Mounting to busbar:

- Be sure that there are no burrs around the hole.
- Length of the screw depends on the busbar thickness.
- Use standard screws, nuts and washers. (Plated with Zn)
- Recommended torque for M12 is 50-75 Nm

OT-Connectors are suitable for Aluminium- and 
Copper conductors.

- Strip cable, see stripping length 

L

1

(table below)

- Remove any layer of oxide.
- Segmental conductors have to be rounded before 
mounting.

- Tighten the screw with torque 

M

- Support connector during tightening.

M12x35/8.8/DIN 933

D12/SFS 3738

D12/DIN 6796 ; SFS 3737

M12/8.0/DIN 934 

D12/SFS 3738

Отзывы: