OUMAN Ouflex A Скачать руководство пользователя страница 18

18

 Settings

Supply water min limit 

12.0 °C  >

     Min lmt increase outd. temp. -20 

3.0 °C  >

Supply water max limit 

42.0 °C  >

 

 I-control ’s max effect on supp. wtr 

2.0 °C  >

 Asetusarvot

Huonelämpötila 

21.0 °C  >

Lämmönpudotus ( huonelämpö ) 

1.5 °C  >

Suuri lämmönpudotus ( huonelämpö ) 

5.0 °C  >

Menoveden minimiraja 

12.0 °C  >

 Settings

Room temperature 

21.0 °C  >

Temperature drop (room temperature ) 

1.5 °C  >

Big temperature drop (room temperature ) 5.0 °C  >
Supply water min limit 

12.0 °C  >

In Ouflex A, settings can be classified into the following categories: 
•  Main settings

•  Hidden settings 

You can hide/show these settings by pressing OK for a few se-
conds. When visible, these settings are shown slightly indented.

•  Settings that require maintenance code 

There is a   symbol in front of these settings. If you try to change 

one of these settings, your Ouflex A device asks you to enter the 
maintenance code.  

Changing a setting: 

Choose the desired setting by turning the control knob. Press OK to go 

to the view where editing is possible. Change the setting.

Press OK to accept the change. 

Press Esc to exit the editing view.

You can see the setting range (minimum and maximum value), if there 

is one, in the editing view.

Locking the settings: 

Lock the settings to prevent unauthorized persons from changing them. 

The device will then ask for lock code before it let’s you change the set-

tings. You can lock the settings in Ouflex A device system settings. 

 Huonelämpötila

21.0°C

min: 0.0  max: 95.0

  Room temperature

21.0°C

min: 0.0  max: 95.0

4 Settings

 

If a GSM modem is connected to Ouflex A device and the setting values have been brought into SMS interface, you can ed-
it settings by text message. Send a message “Key words”. The reply message shows you which key words are in use in the 
application. The example below describes the communication principle. 

Send a message: H1 Settings.

 

The controller sends the main settings to your mobile phone. Editing the setting 
values: write the new setting in place of the old setting and send a message
back to the controller. The controller sends the setting as a return message.

H1 SETTINGS

H2 SETTINGS

H1 Settings:
Room temperature  = 21.5°C/
Temp.drop = 3.0°C/

Содержание Ouflex A

Страница 1: ...enables installation to most common cabinets Detachable strip connectors make installation easier Key words Active alarms Alarm history KEY WORDS Internet based on line control room for professional...

Страница 2: ...hat you seldom need to change or look into makes the HMI simpler When visible this information is shown indented There may be a maintenance code in use in your Ouflex A device In this case you can see...

Страница 3: ...backup and restore factory settings 10 1 8 Log 10 2 Alarms 11 3 Point information 14 3 1 Wiring info 14 3 1 1 Measuring point control manual control 14 3 2 Bus points 14 3 3 Time programs 15 3 3 1 Pre...

Страница 4: ...ce USB host connector Connect the modem power supply to the device conectors 93 and 4 Switch the power on The controller initializes the modem and detects the message center the message not visible on...

Страница 5: ...t automatically Signal strength SMS PIN Modem status Device ID SIM card status Ouman GSM modem is connected to modem using an USB cable The modem has a fixed antenna that can replaced with to an exter...

Страница 6: ...rk cables have not been connected properly Check the network cable connections and or make sure DHCP service is in use 4 If DHCP is On network settings were successfully chanced and the device now fun...

Страница 7: ...ed on the serial number of the Ouflex A device After that you have to activate the ACCESS service from the device OUMAN ACCESS device can be connected to LAN if following condi tions are fulfilled 1 L...

Страница 8: ...or disables the entire Modbus TCP communication A1 B1 RJ45 A2 B2 Modbus TCP IP settings System settings Network settings ModbusTCP IP System settings Network settings SNMP ModbusTCP IP gateway Modbus...

Страница 9: ...Lock code In use Not in use If you take lock code into use you can read Ouflex A device information when the device is locked but you can not change settings It is recom mended for example that you ta...

Страница 10: ...taken lock code into use you may change the code System settings Change lock code Ouflex A device asks you to enter the current code The factory setting of lock code is 0000 Turn the control knob and...

Страница 11: ...s The controller sends a message showing all active alarms Message is informational Alarms Active alarms Alarm history Acknowledge all alarms Reset alarm history Routing schedule Alarm receivers Alarm...

Страница 12: ...h time 1 Press OK at the Add new row 2 Press OK Set the switch time for alarm routing set hours and mi nutes separately and press OK 3 Press OK and then turn the control knob to set the alarm team or...

Страница 13: ...b Press OK to accept a number sign Press OK to move to the next square Press Esc to return to the previous square Press OK for a number of seconds to accept the number Press Esc for a number of second...

Страница 14: ...more detailed information like name and point ID of the measurement point You can also rename the measurement point change device type and activate trend log 3 1 1 Measuring point control manual contr...

Страница 15: ...nt value 3 3 Time programs 3 3 1 Present value Time programs H1 Heating temperature drop Off H2 Heating temperature drop Off Light control On El group 1 control On Heating H1 Temperature drop Present...

Страница 16: ...iew opens and it shows all the switch times and also the states into which the function is driven at these times on the chosen days Turn the control knob to browse a weekly program If you wish to see...

Страница 17: ...select from the following Deleting a control from the exception schedule Select the switch moment to be deleted at mode Delete switch time and select Ready to confirm Deleting a control from the spec...

Страница 18: ...diting is possible Change the setting Press OK to accept the change Press Esc to exit the editing view You can see the setting range minimum and maximum value if there is one in the editing view Locki...

Страница 19: ...DS or Ou01 Capital and small letters are different characters in the device ID The controller sends as a text message a list of keywords that can be used to get information about the controller functi...

Страница 20: ...llation easier Control knob and OK button Info button Detachable connector shield Detachable strip connector shield Acknowledge alarm button Alarm led Display connector RJ 45 connector cab le length m...

Страница 21: ...12 Universal input 13 16 Universal input pulse counter input 21 22 Digital input pulse counter input 2 Detachable strip connectors measurements ground Connector labels Measurements ground 16pcs 1 71 7...

Страница 22: ...0V transmitters 0 4 20mA digital contact input potential free pulse counter first supported passive sensors NTC10 NTC1 8 NTC2 2 and NTC20 Ni 1000 LG Ni 1000 DIN 43760 Pt 1000 FLEX AO8 has 8 analog out...

Страница 23: ...lex Combi 32 is a DIN rail attachable and RS 485 connected univer sal I O extension unit It has 31 pcs I O points and 5 pcs 24Vac out puts and 15Vdc output The device has 16 pcs universal measurement...

Страница 24: ...t be considered when calculating total accuracy Active sensors inputs 1 16 0 10 V voltage message meas accuracy 1 mV Milliampere signal with shunt resistor 0 4 20 mA Contact information inputs 1 16 Co...

Отзывы: