Step 6: Pipe arrangement
• Use suitable connecting pipes and equipment for the
refrigerant R410A.
• The pipes should be placed along the wall,
slightly bent and if possible be hidden.
The minimum bending semi diameter is 4" (100 mm).
• If the outdoor unit is higher than the wall hole,
you must set a U-shaped curve in the pipe before
pipe goes into the house, in order to prevent rain
from getting in.
b
a
e
d
c
L4
L3
L2
L5
L1
Maximum length of connection pipe and maximum height difference
Outdoor unit
Equivalent length of the farthest fitting pipe Lx
Indoor unit
Indoor unit
Height diff
er
enc
e bet
w
een indoor unit and out
door unit H1
Height diff
er
enc
e bet
w
een
indoor units H2
Model #
Max. total length
of connection pipe
L1+L2+L3+L4+L5
Max. length
for single unit
Lx
Max. height
difference
outdoor to
indoor unit
H1
Max. height
difference between
indoor units
H2
ft. (m)
ft. (m)
ft. (m)
ft. (m)
MPD18KCH22SO
66 20
33 10
33 10
33 10
MPD24KCH21SO
197 60
66 20
33 10
33 10
MPD30KCH21SO
230 70
82.5 25
49.5 15
25 7.5
MPD36KCH21SO
246 75
82.5 25
49.5 15
25 7.5
MPD42KCH21SO
246 75
82.5 25
49.5 15
25 7.5
U-shaped curve
wall
drain hose