6.5 Connecting the OTT CBS to LogoSens 2 or DuoSens using a
4 … 20 mA interface
䡵
Connect the OTT CBS to the LogoSens 2 Station Manager or to the DuoSens
Compact Data Logger as shown in Figure 12. Take note of the operating
instructions for the LogoSens 2/DuoSens. Maximum cable length/recommend-
ed cable cross-section: Ensure that the ohm cable resistance together with any
resistor present does not exceed the maximum permitted load resistance (see
Chapter 10)!
Configuring the LogoSens 2/DuoSens for OTT CBS with 4 … 20 mA
interface
䡵
Create a LogoSens 2/DuoSens channel with function block
I 4-20 mA
(LogoSens 2) or
U/I/Pt100/… (DuoSens) (Analog sensors tab).
䡵
Apply the following settings:
䊳
Terminal block
LogoSens 2: A … R
DuoSens:
C ... F
terminal block used (screw terminal strip)
of the LogoSens 2/DuoSens.
䊳
Measuring mode
Set to
I 4-20 mA ext.
(only with DuoSens)
䊳
Sensor lag time (s)
switches on the LogoSens 2/DuoSens input
x seconds before the actual measurement
process; set to
1
Fig. 13: Setting operating parameters of the
LogoSens 2
I 4-20 mA function block.
The DuoSens function block
U/I/Pt100/…
is set in the same way.
4 … 20
m
A
i
n
put
A … R
4
3
1
2
4
3
1
2
LogoSens 2
4 … 20
m
A
i
n
put
C … F*
CBS
4
3
1
2
4
3
1
2
DuoSens
A
CBS
A
100 Oh
m
resistor
* DuoSe
n
s with
a
n
alog exte
n
sio
n
o
n
ly
+U
Bat
GND
+U
Bat
GND
Fig. 12: Connecting the OTT CBS to
LogoSens 2 or DuoSens using a
4 … 20 mA interface.
Use the 100 Ohm OTT resistor
(order number: 55.550.126.4.2)!
The letters above/below the screw terminal
strip identify the possible connections on the
LogoSens 2/DuoSens/CBS.
In the shown application the supply of the
current loop will occur via the OTT CBS.