83 / 120
2018-02-13
Climatix HERU® 400-2400
Miscellaneous
–
Active
–
Calendar time enabled
Choice-x
–
Date
–
Interval
–
WeekDay
–
Passive
Specification of exception type:
–
A certain day (e.g. Friday).
–
A period (e.g. holiday).
–
A certain day of the week.
–
Times are disabled.
This value must always be placed last,
after the date.
-(Start) Date
–
Choice-x = interval: Enter the start
date for the period.
–
Choice-x = date: Enter specific date.)
–
End date
Choice-x = interval: Enter the end date
for the period. The end date must be
later than the start date.
–
Week day
Choice-x = only day of the week: Enter a
day of the week.
Only the time for (start) is relevant.
•
–
(Start)Date = *,01.01.09
Result: 1 January 2009 is an exception date.
•
–
(Start)Date = Mon,*.*.00
Every Monday is an exception date.
•
–
(Start)Date = *,*.Even.00
All days in even months (February, April, June, August, etc) are exception days.
The times for (Start)Date and End Date are applied.
•
–
(Start)Date = *,23.06.09 / -End Date = *,12.07.09
23 June 2009 to 12 July 2009 are exception days (holidays, for example).
–(Start)Date
=
*,23.12.00 /
-
End Date
=
*,31.12.00
23
-
31 December is an exception period every year. Time End Date = *,01.01.00 does
not work, because 1 January comes before 23 December.
•
–
(Start)Date = *,23.12.09 / -End Date = *,01.01.10.
23 December 2009 to 1 January 2010 are exception days.
•
–
(Start)Date = *,*.*.00 / -End Date = *,*.*.00
Warning! This means that the exception is always active! The unit is constantly in
exception mode or switched off.
The times for days of the week are applied.
•
Day of the week = *,Fr,*
Every Friday is an exception day.
•
Day of the week = *,Fr, Even
Every Friday in even months (February, April, June, August, etc) is an exception day.
•
Week day = *,*,*
Warning! This means that the exception is always active! The unit is constantly in
exception mode or switched off.
Configuration
The unit is configured according to preferences. Configuration includes the following
three steps:
Example:
Choice-x = Date
Example:
Choice-1 = Interval
Example:
Choice-1 = Day of the
week
Configuration
Principle
Содержание HERU 400-2400 S
Страница 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Страница 2: ......
Страница 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Страница 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Страница 65: ...65 120 2018 02 13 Climatix HERU 400 2400 External components basic unit 994020653 CLIMATIX HMI DM Display IP31...
Страница 95: ...95 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Alarm button function Procedure for non saving alarms...
Страница 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Страница 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Страница 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Страница 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Страница 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Страница 119: ......
Страница 120: ......