Osram ENCELIUM EXTEND Manager Скачать руководство пользователя страница 3

3

GreenBus II must be laid out as per ENCELIUM EXTEND LMS supplied drawing.  
If changes are required, determine an optimum wiring path utilizing the supplied 
prefabricated cables, based on the position of light fixtures and sensors. As the 
modules obtain power via the GreenBus II, the number of modules on each chain is 
limited. It is suggested to leave room for future system upgrades and to limit the 
number of modules per chain to 100 units during initial installation.

GreenBus II Wiring 

Communication Circuit (24V

dc

, Class 2)

GreenBus II

®

 is a low-cost, high reliability communication means to report sensor 

information back to the ENCELIUM

®

 EXTEND Networked Light Management  

System (LMS) and to obtain optimum brightness settings for light fixtures from the  
system – optimized to result in minimum energy costs for any given building. 
The GreenBus II wiring originates at an ENCELIUM EXTEND Manager and 
propagates in a daisy-chain or “T” fashion from module to module (or other 
compatible equipment). 

GreenBus II uses proprietary connectors and jacks for ease of installation 
only. GreenBus II is a proprietary standard. Connect to ENCELIUM EXTEND 
Networked Light Management System only. Do not connect to other circuits.

Connect to ENCELIUM EXTEND Networked Light Management 
System only. Do not connect to other circuits.

Maximum 100 total devices

Manager Installation 

The output channels of the Manager are Class 2 circuits.

To reduce the risk of electric shock, the power supply for the equipment has a 
grounding type plug that has a third (grounding) pin. This plug will only fit into a 
grounding type outlet. If the plug does not fit into the outlet, contact a qualified 
electrician to install the proper outlet. Do not change the plug in any way.

Use only the power supply provided for this equipment. Damage or adverse 
functionality may occur if a different power supply is used. If a replacement 
power supply is needed, please contact OSRAM SYLVANIA Inc. Do not 
modify the power supply cable or connector.

The Manager is intended for mounting in an electrical room where access 
will be by authorized personnel only.