Osram 4008321189721 Скачать руководство пользователя страница 8

APPLICATIONS DALI MCU 

 

7. Other fields of application

 

 

Consider you have a similar room with a retractable dividing 

wall, such as a conference room, a public hall or a 

restaurant. When the dividing wall is closed, you want both 

sections of the room to be individually dimmable and you 

want to be able to switch lights off/on in either section 

independently. When the dividing wall is open, however, you 

want to control lighting synchronously across the entire room 

(both sections) from any of the control points. To achieve 

this, you would set up one DALI control circuit in each of the 

sections You would then connect one control device in each 

section (figure 5) to the mains, and optionally, you could also 

install a second control device without mains connection in 

each of the sections. 

 One DALI MCU control device in each of the two sections 

must have a mains connection to make sure that it can 

supply its assigned control circuit when the dividing wall is 

closed. 

When the dividing wall is closed, the position switch is in 

open position, so the connection between the two control 

circuits is broken. Then, lighting can be controlled and 

dimmed in both sections independently.  

When the dividing wall is open, the position switch is in 

closed position and the control circuits in both sections and 

their corresponding control points are turned into one single 

parallel-connected control circuit. You will therefore be able 

to control all lamps in both sections simultaneously. Please 

pay special attention when connecting the control lines to the 

terminals of the DALI MCUs (polarity!). Single-pole 

interruption of the DALI control line via the position switch is 

generally permissible. It does not matter, which of the two 

control wires (Da+ or/and Da-) is used for switching or 

whether both are used. As soon as the previously closed 

dividing wall is opened – connecting the previously 

interrupted DALI cable between the control devices in both 

sections – illumination levels in both sections will adjust to a 

uniform brightness within approx. 10 seconds. The 

brightness level will match the level previously set in one of 

the sections. Turning the knob on any of the DALI MCUs will 

then change the lighting in the entire room based on this 

previous level. 

 

Figure. 5: DALI wiring layout in a dividable room 

 

8

 

Содержание 4008321189721

Страница 1: ...changed at either of the control devices With the DALI MCU digital potentiometer it is easy to meet such requirements The parallel connection between the two devices control points which would be requ...

Страница 2: ...the command triggered by the device last operated will determine the current switching state and or the brightness value in the room At the same time the command is transmitted to the other devices w...

Страница 3: ...single pressure of the rotary knob and by turning the rotary knob to the left or right you can set the required brightness value Moreover you can also ask the DALI MCU to store a particular brightnes...

Страница 4: ...me control circuit With this setup you can control up to 25 ECG independent of their power consumption Each DALI ECG comes with the interface that has a power consumption of approx 2mA The internal po...

Страница 5: ...also connect the second control device to the 230V mains you can operate up to 50 luminaires and two additional DALI MCUs without mains connection in one and the same control circuit i e 4 control poi...

Страница 6: ...exceed 300m It is important to observe correct polarity of the feed cables when connecting the control line with two or more DALI MCU control devices Because each of the devices has its own power sup...

Страница 7: ...n also reset the system to its default setting in which the brightness value used before switching off the light will be restored when the light is switched back on the next time To do so switch off t...

Страница 8: ...nnection between the two control circuits is broken Then lighting can be controlled and dimmed in both sections independently When the dividing wall is open the position switch is in closed position a...

Страница 9: ...clude dimmable individual luminaires groups of luminaires custom settings in RGB colour mix systems with designer lamps or decorative lamps and the control of fluorescent lamps with different colour t...

Страница 10: ...connection L N Operating voaltage 230 V AC 50 60 Hz Power consumption 3 W max DALI connection da da max 300 m cable legth 25 DALI ECG max Perm Cable cross section 1 4 mm 2 Ambient temperature 0 50 C T...

Отзывы: