Osram 4008321189721 Скачать руководство пользователя страница 1

 

1

 

www.osram.com/ecg-lms 

 

 

Professional-Practice 

DALI MCU: Digital potentiometer with DALI

 

 

Manual lighting control with the DALI MCU for rooms with grouped luminaires with 
as many as 50 ECG, with or without dividing wall

 

 
 1. 

Application

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

Consider you want to switch on/off and dim the light 

in a room, a restaurant or bar, a foyer or lounge etc 

– but you want to do it from either of its two doors, 

no matter which. For this to work, the two control 

points would have to operate synchronously in such 

a fashion that the lighting system responds 

immediately and harmoniously when the brightness 

level is changed at either of the control devices. 

 

 

With the DALI MCU digital potentiometer, it is easy 

to meet such requirements.  

 
 

 

 

The parallel connection between the two devices 

(control points), which would be required for our 

example to work, becomes super simple – and it 

does not necessitate any demanding installations 

and/or additional control components. 

 

 

Each control circuit simultaneously affords the 

integration of as many as 50 luminaires and of up to 

4 DALI MCU control devices (control points). And all 

that while allowing for the required comfortable, 

easy and complete control over the lighting levels at 

any time. 

03 

User benefits 

04 

Installation 

05 

Wiring for a  
conference room 

06 

Operation 

07 

Other fields of application

08 

Technical data

 

 

Content 

 
 

01 

Application 

02 

Setup/Function of 
components 

Содержание 4008321189721

Страница 1: ...changed at either of the control devices With the DALI MCU digital potentiometer it is easy to meet such requirements The parallel connection between the two devices control points which would be requ...

Страница 2: ...the command triggered by the device last operated will determine the current switching state and or the brightness value in the room At the same time the command is transmitted to the other devices w...

Страница 3: ...single pressure of the rotary knob and by turning the rotary knob to the left or right you can set the required brightness value Moreover you can also ask the DALI MCU to store a particular brightnes...

Страница 4: ...me control circuit With this setup you can control up to 25 ECG independent of their power consumption Each DALI ECG comes with the interface that has a power consumption of approx 2mA The internal po...

Страница 5: ...also connect the second control device to the 230V mains you can operate up to 50 luminaires and two additional DALI MCUs without mains connection in one and the same control circuit i e 4 control poi...

Страница 6: ...exceed 300m It is important to observe correct polarity of the feed cables when connecting the control line with two or more DALI MCU control devices Because each of the devices has its own power sup...

Страница 7: ...n also reset the system to its default setting in which the brightness value used before switching off the light will be restored when the light is switched back on the next time To do so switch off t...

Страница 8: ...nnection between the two control circuits is broken Then lighting can be controlled and dimmed in both sections independently When the dividing wall is open the position switch is in closed position a...

Страница 9: ...clude dimmable individual luminaires groups of luminaires custom settings in RGB colour mix systems with designer lamps or decorative lamps and the control of fluorescent lamps with different colour t...

Страница 10: ...connection L N Operating voaltage 230 V AC 50 60 Hz Power consumption 3 W max DALI connection da da max 300 m cable legth 25 DALI ECG max Perm Cable cross section 1 4 mm 2 Ambient temperature 0 50 C T...