
Page 32
Installation and Operation Manual - Inspire 2000
8.3 Floor Protector
If the wood fire is to be installed on top of a combustible floor, it must be guarded by a non
combustible material as shown on the dotted line area of the above figures. Install a 844 mm
(Wide) x 1050 mm (Deep) floor protection of 9 mm of thickness with thermal conductivity of 0.1
m2 K/W per 9 mm thick.
FLOOR PROTECTION
3
D
300 mm
E
200 mm
4
D
E
Figure 31: Floor Protection
8.4 Reducing Wall and Ceiling Clearances Safely
You may decrease the minimum clearances
to heat-sensitive materials by installing heat
radiation shields between the walls or the ceiling
and the wood fire. These heat radiation shields
must be installed permanently and must be made
of a heat-resistant or heat-tolerant material.
An air gap must separate the heat shield from
any heat-sensitive surface. Furthermore, the
heat shield shall extend in all directions beyond
the boundaries of the appliance surface by a
distance of not less than 450 mm.
Exceptions
may apply. Refer to AS/NZS 2918:2001.
Figure 32: Heat shield
Following the installation of such heat radiation shields, the minimum clearances to heat-sensitive
materials may be reduced by applying the clearances factor in the table below:
3 Cement fibre sheet or similar. No protection is required if the unit is installed on a non-combustible floor (ex: concrete).
4 The floor protector shall extend not less than 200 mm from each side of any ash removal or fuel loading openings unless the floor protector forms
an abutment with a wall or heat shield at a lesser distance.