 Reliability and life of the product are provided not only by the quality of product itself,

but   also   by  the   compliance   with   operating   modes   and   conditions,  therefore,  this   document

requirements is mandatory

“Lun-7Т”

тм

/”Lun-73Т”

GSM Wireless Communication Channel Control Panel

Installation Manual

ORTUS Group

Product Compatibility Table

GSMControl Panel

«Lun-7Т»

тм

«Lun-73Т»

Version

GSM Control Panel Confguration

Software

"Confgurator"

Version

Central Monitoring Station

“Orlan-M11” modules-

based Orlan

Version

Содержание LUN-7T

Страница 1: ...and conditions therefore this document requirements is mandatory Lun 7 Lun 73 GSM Wireless Communication Channel Control Panel Installation Manual ORTUS Group Product Compatibility Table GSMControl Pa...

Страница 2: ...9 ICD indicators 14 9 2 3 Indication of troubles faults on Lind 9 ICD 14 9 2 4 Supervisor and Installer passwords 14 9 2 5 Manual password control 15 9 2 6 Confguring of device from keypad 16 9 2 7 A...

Страница 3: ...d on the safety arrangements and having the permit to work with electrical installations of up to 1000V shall be allowed to install routinely maintain and repair the device GOST 12 3 019 80 SNiP 3 05...

Страница 4: ...es of the supply circuits 4 Set and connect the zone resistors and switch boxes to the wires of detectors Connect the wires of supply circuits to the circuit breakers 5 Check the operational integrity...

Страница 5: ...h device shuts down V 10 5 Maximum length of communication line between the Control Panel and Lind 7 indication and control device when using the cable of foiled twisted pair type with cross section o...

Страница 6: ...7 k ACT Prime power supply control line only for Lun 7 12V 14 Device power voltage GND Common contact of device GND Common contact of device MON2 Line of communication with Lun 7N Lun 73N network dev...

Страница 7: ...his purpose Tamper contacts of power supply unit Lind 7 indication and control devices switched spur and all detectors connected to the Control Panel shall be connected to this zone Attention Tamper z...

Страница 8: ...iiure 1 Appearance of Lind 7 ICD The front panel of the indication and control device has the following elements ZONE 1 8 red LEDs security zone status indicators Activated detector zone is displayed...

Страница 9: ...trol Panel with intermittent beeps Beeps will stop when the authorized user key touches Touch Memory key reader ICD has a button of tamper contact inside responding when ICD is uncovered To provide th...

Страница 10: ...3 LED when TROUBLE button is pressed and held 5 Local bus trouble is displayed by frequent fashing of SYSTEM LED and glowing of ZONE 4 LED when TROUBLE button is pressed and held This fault shows that...

Страница 11: ...case the following shall be checked 1 1 Signal level and signal quality at the Control Panel s remote antenna installation place 2 2 CMS connection confguration settings 9 1 5 Disarming 1 To disarm t...

Страница 12: ...t in the armed state EVENT REPORTING red LED displays the message transmission to CMS and shows there are not sent events in the memory ZONE 1 8 red LEDs zone status indication Glowing LEDs indicate t...

Страница 13: ...When the button is pressed the power is supplied to all LED indicators of Lind 9 to control their operability Active for any user Single pressing of this button cancels the commands inputted on the ke...

Страница 14: ...ower fault 230V is displayed by fashing of FAULT and POWER 220V LEDs 2 Battery discharged or No battery is displayed fashing of FAULT and BATTERY LEDs 3 No CMS connection is displayed by fashing of FA...

Страница 15: ...rol To set and change passwords manually 5 combination is used after which the Supervisor s password in our example it s 1253 is entered When the above mentioned combination is being inputted the keyp...

Страница 16: ...Exit 5 1253 01 1546 02 2357 03 7852 9 To delete a password you shall log in under the supervisor s password select the number of password and input 1 deletion command The sequence of operations to de...

Страница 17: ...LEDs will fash shortly several times and extinct Number of remote LED s fashes 1 8 indicates the frst number of the detector zone alarmed If there are 9 fashes it means that arming is prohibited In c...

Страница 18: ...Attention In any case when the siren is enabled typing of the authorized four digit code on the keypad will disable it 10 Confguring from computer Device confguration is performed through the contact...

Страница 19: ...armed with one or several violated zones Armed with alarms report is sent If Control Panel is not armed and none of 24 hour zones is violated a Not armed with no alarms report is sent If Control Panel...

Страница 20: ...anders to increase the number of the Control Panel groups Each expanders an independent protective group which has its own means of control and indication however these devices have no individual mean...

Страница 21: ...ional capabilities of the burglar alarm system it allows enabling or disabling of equipment in the facility as well as to duplicate the status of zones and events occurred by means of eight built in r...

Страница 22: ...he manufacturer s package 19 Transportation 1 Product transportation shall be carried out in the manufacturer s package 2 Product is allowed to be transported by all types of enclosed transporters sub...

Страница 23: ...tion of the existing Lun 7T Control Panel namely Integrated GSM module with antenna Integrated main power monitoring circuit Integrated charge controller processor in TQFP enclosure All the functions...

Страница 24: ...n circuit Description Connection of zone termination resistor when using normally open contacts Connection of zone termination resistor when using normally closed contacts Connection of zone terminati...

Страница 25: ...Failure to comply with this requirement may lead to warranty disclaimer Fiiure 6 Diairam of connection of external devices and detectors without Lind control and indication device by usini the armini...

Страница 26: ...c circuit diagram is mandatory Failure to comply with this requirement may lead to warranty disclaimer Fiiure 8 Diairam of connection of external devices and detectors usini Lind 7 indication and cont...

Страница 27: ...mandatory Failure to comply with this requirement may lead to warranty disclaimer Fiiure 9 Diairam of connection of external devices and detectors usini Lind 9 indication and control device Fiiure 10...

Страница 28: ...trol relay usini third party power supply units Attention Adherence to this electric circuit diagram is mandatory Failure to comply with this requirement may lead to warranty disclaimer Fiiure 12 Exte...

Страница 29: ...e electric circuit diagrams is mandatory Failure to comply with this requirement may lead to warranty disclaimer Fiiure 13 MPB 8 module connection diairam Fiiure 14 Phone communicator connection diair...

Страница 30: ...Fiiure 15 Place of installation of device assemblies for monoblock unit version 425523 003 Rev en_19 30...

Страница 31: ...Fiiure 16 Mountini elements for sinile unit housini version 425523 003 Rev en_19 31...

Страница 32: ...Fiiure 17 Installation of anti obstruction contacts in version sinile unit housini 425523 003 Rev en_19 32...

Страница 33: ...Fiiure 18 eequence of power supply unit installation for sinile unit housini version Fiiure 19 Lind 7 ICD uncovered Fiiure 20 Lind 9 ICD uncovered rear view 425523 003 Rev en_19 33...

Страница 34: ...lfunction of the Equipment 8 Manufacturer shall not be liable under the Warranty if the test and or analysis conducted by the Manufacturer shows that the product has no claimed defect or it that this...