TROUBLESHOOTING

Instruction Manual

1-888-543-6473
1-888-541-6474

13376 Comber Way 

Surrey BC V3W 5V9

[email protected] 
www.ortechindustries.com

375 Admiral Blvd

 

Missis

s

auga

ON L5T 2N1

LED Emergency Lights

MODEL

 

O

E-212BP

Emergency Lamps 

come on dim when test button is pressed

:

Battery discharged — permit unit to charge for 20 hours and then retest. If lamps are still dim, check charger for proper 
function. If charger functions correctly, replace battery.

Emergency Lamps 

come on when battery is first connected

:

Batt

ery may be connected in reverse polarity

.

 Check connections. Connect Positive (+) lead to Positive (+) battery terminal 

and Negative (-) lead to Negative (-) battery terminal. The lamps should then turn OFF and the charge indicator should light 
when AC power is applied (see Fig.3 on page 2 of this instruction manual).

Emergency Lam

ps come on dim when AC power is ON

:

1. Check supply voltage and AC connections. This emergency light is provided with brownout protection.

The AC supply must be at least 80% of nominal (120V on a 347V) for equipment to function normally.

2. At lower voltages, the emergency lamps will begin to glow dimly until the source voltage drops below the full turn-on point.

NOTE — This condition may also be caused by incorrectly connecting a 120V supply to the 347V transformer lead.

Nothing happens when the unit is energized:

Some model have a standard time delay built into the design of the charger board. Please allow 15 minutes with AC current 
connected. At this point, the LED AC-ON and CHARGE lights should illuminate.  

IMPORTANT REMINDER

**BATTERY VOLTAGE IS NEGATIVELY RELATIVE TO INPUT WATTAGE.

OE-212BP is constructed with steel housing and lightweight thermal plastic head in matching colour. It has simple and 
modern design with high efficiency LED remote heads. Universal mounting pattern and keyhole slots are stamped on 
the back and conduit knockouts on the sides of each unit.