IG-308-EN version 01; 03/06/2022
45
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Recommended sequence of operations
5.5.5. Opening operation from closed position
Initial conditions:
circuit-breaker closed, earthing
switch open and springs charged.
1.
Open the circuit-breaker by pressing the "0" opening
button and check the status indicating relay.
Figure 5.28.
Opening button detail
2.
Check there is no voltage through the
ekor
.vpis or
ekor
.ivds.
3.
Move the access handle in the grey zone to its bottom
position.
Figure 5.29.
Handle detail