IG-308-EN version 01; 03/06/2022
39
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Recommended sequence of operations
5.4.7. Cable test
These driving mechanisms allow the operation of going
from earthing switch closed to switch-disconnector
open, even when the cable compartment cover is
open. The switch-disconnector cannot therefore be
changed to closed position until this cover has been
put back.
The cable test can only be carried out in feeder
functions which include B/BM driving mechanisms
with this characteristic. Please check with
Ormazabal
.
1.
Follow the steps in section "5.4.6. Earthing operation
2.
Leave the lever in the earthing switch access (yellow
area).
3.
Open the bottom cover to access the cable
compartment.
4.
With the lever in the earthing switch access, follow
the steps in section "5.4.3. Opening operation from
5.
Carry out the cable test.
6.
To return to earthing position, follow the steps in section
"5.4.6. Earthing operation from isolating position".
7.
Close the bottom cover to access the cable
compartment.