Alentec & Orion AB
Grustagsvägen 4, SE-13840, Älta, SWEDEN · [email protected] · www.alentec.com
10
CONFIGURATION / KONFIGURATION
STEP / STEG
INSTRUCTION
INSTRUKTION
26
Verify that the switches to the right of the display are
set as shown:
Säkerställ att brytarna till höger om displayen ser ut enligt bilden:
APPLICATION SPECIFIC DATA
FASTSTÄLLANDE AV APPLIKATIONSDATA
EN
SE
Frekvensomriktaren är nu redo att sättas i drift. Tryck på AUTO ON för att
sätta anläggningen i drift. The frequency converter is now ready to operate.
Press AUTO ON to start the system.
•
When starting up the system a fine tuning of the Set value, parameter
20-21 will be needed. This is to ensure that correct flow rate is
achieved at all extraction points.
•
After fine tuning the pressure transmitter and frequency converter will
automatically adjust the fan speed (air flow) depending on how many
extraction points are in use.
•
If an mechanical filter is used in the system, the pressure transmitter
and frequency converter will continously adjust the fan speed to
compensate for the particles collected in the filter (pressure drop
across filter cartridge increases).
•
At self-oscillation, change parameter 3.12.1.2 from 1 to 5 seconds.
Frekvensomriktaren är nu redo att sättas i drift. Tryck på AUTO ON för att
sätta anläggningen i drift.
•
Vid uppstart av anläggningen krävs en injustering av Börvärde,
parameter 20-21. Detta för att fastställa att korrekt flöde erhålls vid
samtliga utsugspunkter.
•
Efter injustering kommer TG- trycktransmittern och DCV controllern
att automatiskt reglera fläktvarvtalet (luftflödet) beroende på antal
utsugspunkter som är öppna.
•
Om mekaniskt filter används i anläggningen kommer TG-
trycktransmittern och DCV-controllern att reglera varvtal på fläktmotor
löpande allteftersom filtermediat blockeras av uppsamlade partiklar,
(tryckfallet över filterenheten ökar).
•
Vid självsvängning, ändra parameter 3.12.1.2 från 1 till 5 sekunder.
START UP
DRIFTSÄTTNING
EN
SE