CONFIGURATION / KONFIGURATION

STEP / STEG

INSTRUCTION

INSTRUKTION

26

Verify that the switches to the right of the display are 

set as shown:

Säkerställ att brytarna till höger om displayen ser ut enligt bilden:

APPLICATION SPECIFIC DATA

FASTSTÄLLANDE AV APPLIKATIONSDATA

EN

SE

Frekvensomriktaren är nu redo att sättas i drift. Tryck på AUTO ON för att 

sätta anläggningen i drift. The frequency converter is now ready to operate. 

Press AUTO ON to start the system.

• 

When starting up the system a fine tuning of the Set value, parameter 

20-21 will be needed. This is to ensure that correct flow rate is 

achieved at all extraction points.

• 

After fine tuning the pressure transmitter and frequency converter will 

automatically adjust the fan speed (air flow) depending on how many 

extraction points are in use.

• 

If an mechanical filter is used in the system, the pressure transmitter 

and frequency converter will continously adjust the fan speed to 

compensate for the particles collected in the filter (pressure drop 

across filter cartridge increases).

• 

At self-oscillation, change parameter 3.12.1.2 from 1 to 5 seconds.

Frekvensomriktaren är nu redo att sättas i drift. Tryck på AUTO ON för att 

sätta anläggningen i drift.

• 

Vid uppstart av anläggningen krävs en injustering av Börvärde, 

parameter 20-21. Detta för att fastställa att korrekt flöde erhålls vid 

samtliga utsugspunkter.

• 

Efter injustering kommer TG- trycktransmittern och DCV controllern 

att automatiskt reglera fläktvarvtalet (luftflödet) beroende på antal 

utsugspunkter som är öppna. 

• 

Om mekaniskt filter används i anläggningen kommer TG- 

trycktransmittern och DCV-controllern att reglera varvtal på fläktmotor 

löpande allteftersom filtermediat blockeras av uppsamlade partiklar, 

(tryckfallet över filterenheten ökar).

• 

Vid självsvängning, ändra parameter 3.12.1.2 från 1 till 5 sekunder.

START UP

DRIFTSÄTTNING

EN

SE

Содержание 84370

Страница 1: ...entec Orion AB Grustagsv gen 4 SE 13840 lta SWEDEN info alentec se www alentec com USER MANUAL BRUKSANVISNING Part No Art Nr R f 84370 84371 84372 84373 84374 FREQUENCY INVERTER FREKVENS OMRIKTARE 105...

Страница 2: ...Alentec Orion AB Grustagsv gen 4 SE 13840 lta SWEDEN info alentec se www alentec com 2 EXHAUST CONNECTIONS AVGASANSLUTNINGAR...

Страница 3: ...lt the freqency converter manual TECHNICAL DATA PRESSURE TRANSMITTER 83015 Measuring range 0 3000 Pa Enclosure IP54 Output signal 4 20mA alternatively 0 10V Supply voltage 24 VDC TECHNICAL DATA FREQUE...

Страница 4: ...dbook FUNCTION The Frequency Converter will operate your process ventilation by monitoring the air pressure of your system The Frequency Converter will only run the fans to meet the demand of your pro...

Страница 5: ...smitter Tryckgivare Pressure transmitter Tryckgivare Front Side Sida To fit pressure hose 6mm Tryckslang 6mm Connect MINUS to duct Anslut MINUS till kanal Do not connect Ansluts ej Pressure hose Tryck...

Страница 6: ...standard motors can be used with the frequency converter The direction of rotation should be changed by switching two phases in the motor cable Do not use the frequency inverter REVERSE function to ac...

Страница 7: ...the minus 3 side again Inst llning av m tomr de d mpning Val av tryckomr de sker med jumper p kretskortet enligt figur nedan M tomr det skall ligga s n ra verkligt v rde som m jligt f r att stadkomma...

Страница 8: ...Please observe that these times are unique for each installation and motor General example a 4kW motor ramp up time 5s ramp down time 5s Underl t ej att fylla i nedanst ende v rden De kan beh vas uti...

Страница 9: ...ill p1 5 st ll in cosfi enligt motorns m rkskylt 11 P1 6 Set engine power P1 6 st ll in motorns m rkeffekt 12 P1 13 Acceleration time should be set to 5s P1 13 Accelerationstid ndras till 5 s 13 P1 17...

Страница 10: ...points are in use If an mechanical filter is used in the system the pressure transmitter and frequency converter will continously adjust the fan speed to compensate for the particles collected in the...

Отзывы: