![ORION ITALIA IPR-D Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/orion-italia/ipr-d/ipr-d_instruction-manual_1653248031.webp)
Chapter 4: "SETPOINTS" Menu
CURRENT PROTECTION RELAY - IPR-D
Manual P/N: IPR-D GBM 01/09/2006
4.7
4.6 Setpoint page 6: DIGITAL INPUTS
SETPOINT PAGE 6
DIGITAL INPUTS
This PAGE allows setting the digital inputs.
INPUT 1 FUNCTION
BREAKER EARTHED
RANGE:
.................................
NONE; BREAKER EARTHED; EXTERNAL RESET;
REMOTE TRIP; BLOCK TRIP; ACTIVATE AUX1;
ACTIVATE AUX2; ACTIVATE AUX3
Select the function to be associated with INPUT 1.
INPUT 1 ACTIVE
WHEN: CLOSED
RANGE:
..........................................................................................
CLOSED; OPENED
Configure digital input INPUT 1:
CLOSED
⇒
INPUT 1 will be active when the related contacts are closed.
OPENED
⇒
INPUT 1 will be active when the related contacts are open.
INPUT 2 FUNCTION
EXTERNAL RESET
RANGE:
.................................
NONE; BREAKER EARTHED; EXTERNAL RESET;
REMOTE TRIP; BLOCK TRIP; ACTIVATE AUX1;
ACTIVATE AUX2; ACTIVATE AUX3
Select the function to be associated with INPUT 2.
INPUT 2 ACTIVE
WHEN: CLOSED
RANGE:
..........................................................................................
CLOSED; OPENED
Configure digital input INPUT 2:
CLOSED
⇒
INPUT 2 will be active when the related contacts are closed.
OPENED
⇒
INPUT 2 will be active when the related contacts are open
.
INPUT 3 FUNCTION
NONE
RANGE:
.................................
NONE; BREAKER EARTHED; EXTERNAL RESET;
REMOTE TRIP; BLOCK TRIP; ACTIVATE AUX1;
ACTIVATE AUX2; ACTIVATE AUX3
Select the function to be associated with INPUT 3.
INPUT 3 ACTIVE
WHEN: CLOSED
RANGE:
..........................................................................................
CLOSED; OPENED
Configure digital input INPUT 3:
CLOSED
⇒
INPUT 3 will be active when the related contacts are closed.
OPENED
⇒
INPUT 3 will be active when the related contacts are open
.
END OF PAGE
Last LINE of PAGE 6.
Press
LINE
or
▲
PAGE,
to pass to the first line of PAGE 7.
4.7 Setpoint page 7: EVENT RECORDER
SETPOINT PAGE 7
EVENT RECORDER
This PAGE allows to enable/disable the recording of the events, up to 10 max., according
to FIFO (First-In, First-Out) mode. Once 10 events are stored, the oldest event is cleared
by the new one occurred.
Gnd. PROTECTIONS
EVENTS: ON
RANGE:
.................................................................................................................
ON; OFF
It enables/disables ground current protection events recording.
SYSTEM ALARM
EVENTS: ON
RANGE:
.................................................................................................................
ON; OFF
It enables/disables alarms events recording.
OUTPUT RELAYS
EVENTS: ON
RANGE:
.................................................................................................................
ON; OFF
It enables/disables output contacts events recording.
Содержание IPR-D
Страница 2: ......
Страница 4: ......
Страница 24: ......
Страница 34: ......
Страница 38: ......
Страница 40: ......
Страница 42: ......
Страница 44: ......
Страница 49: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 5...
Страница 50: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 6...
Страница 51: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 7...
Страница 52: ......