The following inputs and outputs are available on the VAV/Zone 

Controller and the OE325-01 Zone Controller Expansion Module. For 

component locations of the inputs on the VAV/Zone Controller and VAV 

Zone Controller Expansion Module see 

Figures 3, 4, and 6

. For wiring 

of inputs and outputs, see

 Figures 7

 

through 13

.

VAV/Zone Controller Analog Inputs

Space Temperature

The Modular Room Sensor that reads space temperature is attached 

to this input. The Modular Sensor connects via a modular cable to the 

Non-Modular VAV/Zone Controller Actuator Package. 

Airflow Sensor

If the OE744-32-VAVZ Non-Modular VAV/Zone Controller Actuator 

Package is being used, the terminal unit’s pressure pick-up tube must be 

connected with FRP tubing to the barb fittings on the side of the enclo

-

sure.  This pressure sensor input is used for CFM (airflow) calculations. 

If an Airflow Sensor is attached to this input, the VAV/Zone Controller 

will automatically detect this and switch to pressure independent opera-

tion. If the sensor is not attached or becomes defective, the controller 

automatically reverts to pressure dependent operation. 

Supply Air Temperature Sensor

A Supply Air Temperature Sensor can be connected to these terminals. It 

should be mounted in the supply duct close to the terminal unit where the 

VAV/Zone Controller is installed. This sensor can be used for monitor-

ing purposes or in place of the Supply Air Temperature Broadcast from 

the VCM-X Controller.

Other Controller Connections

Expansion Board Modular Connector

This modular connector is used to connect the optional  OE325-01 Zone 

Controller Expansion Module to the Non-Modular VAV/Zone Controller 

Actuator Package. This module is only required when electric or hot 

water heating and/or fan terminal control is required. The Expansion 

Module is not required for cooling only terminal units.

Actuator Modular Connector

This modular connector is used to connect a modular cable from the 

VAV/Zone Controller to a tri-state actuator. 

24 VAC Power Terminal Block

This two pole terminal block is used to wire the 24 Volt power to the 

Non-Modular VAV/Zone Controller Actuator Packages If desired a 

single transformer can be used to power multiple VAV/Zone Controller 

Actuator Packages together, or a separate transformer can be used for 

each controller. 

Warning:

 If multiple controllers are to be wired to the same  

    

transformer, polarity must be observed or damage  

    

to the controller will result.

 

Communications Terminal Block

This three pole terminal block is used for connecting the communica-

tions wiring between each Non-Modular VAV/Zone Controller Actuator 

Package and/or to the MiniLink Polling Device, CommLink, HVAC 

Unit Controller or other  controller on the local communications loop. 

Communications wiring should be 18 gauge 2 conductor twisted pair 

with shield Belden #82760 or its equivalent.

Modular Service Tool DIN Connector

This connector is used to connect a cable between the  Modular Service 

Tool or the USB-Link and the Non-Modular VAV/Zone Controller 

Actuator Package for programing and configuration of the VAV/Zone 

Controller.

OE325-01 Zone Controller Expansion 
Module

As previously stated, when control of a fan or if heating is required, the 

OE325-01 Zone Controller Expansion Module is required.

Relay Output #1 - Fan Enable

The first expansion relay on the Output Expansion boards is used for 

energizing the fan on Series or Parallel Fan Terminal Units. 

Relay Output #2 - Heating Stage 1

If you have at least one stage of  heating, this is the relay used to energize 

the 1st stage of terminal unit heating. This heating stage can either be 

used with electric heat or On/Off hot water valve control.

Relay Output #3 - Heating Stage 2

If you have two stages of electric heating, this relay controls the 2nd 

stage of electric heat. For 3 stage heating, this relay output would be 

energized for both the 2nd and 3rd stage of heat. See the following 

paragraph for more information regarding 3 stage heating applications.

3 Stage Heating Applications

If three stages of electric heat are configured, relays #2 and #3 will stage 

in a staggered sequence. This allows you to achieve 3 stages of heating 

using only relays #2 and #3. Each of the 3 heating elements should be 

sized for one third of the total KW output required. Both the 2nd and 3rd 

stage heating contactors (C2 & C3) must be connected to Relay Output 

#3. See 

Table 1

 below for relay sequencing information.

Relay Staging

Stage No.

Relay Output #2

Relay Output #3

1

VAV/Zone Controller 

Package ON (C1)

OFF (C2 & C3)

2

OFF (C1)

ON (C2 & C3)

3

ON (C1)

ON (C2 & C3)

Table 1:  Relay Sequencing For 3 Stage Heating

Auxiliary Heat Relay

If you have an auxiliary heat source you would like to control in addition 

to or in lieu of the other heat options, you can connect it to relay R4 on 

the expansion module. This relay has a separate setpoint available for 

controlling an electric baseboard or duct heater or a two position hot 

water valve for a baseboard radiator or duct heater.

 

Analog Output

If you are using hot water or steam heating via a modulating steam 

or hot water valve, this output can supply a 0-10 Volts DC signal for 

proportional control of the valve.

Inputs and Outputs

8

                                                                              

Non-Modular ZCAP Technical

 Guide

Overview

Содержание OE742-32-VAVZ

Страница 1: ...Non Modular VAV Zone Controller Actuator Package www orioncontrols com...

Страница 2: ...16 Addressing Powering Up 17 General 17 Controller Addressing 17 Power Wiring 17 Initialization and Programming 18 Initialization 18 Programming the Controller 18 VAV Zone Configuration 19 VAV Zone C...

Страница 3: ...oused in a plastic enclosure The VAV Zone Controller is a program mable digital controller which allows for program setpoints to be stored in non volatile memory The controller is connected to a room...

Страница 4: ...Figure 1 OE742 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P D Non Modular VAV Zone Controller Actuator Package Dim P D 4 Non Modular ZCAP Technical Guide Overview...

Страница 5: ...Non Modular VAV Zone Controller Actuator Pkg P I Figure 2 OE744 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P I 5 Non Modular ZCAP Technical Guide Overview...

Страница 6: ...ar VAV Zone Controller Actuator Pkg Components Non Modular VAV Zone Controller Actuator Package Components Figure 4 OE744 32 Pressure Independent Non Modular VAV Zone Controller Actuator Pkg Component...

Страница 7: ...5 01 Zone Controller Expansion Module Dimensions Figure 6 OE325 01 Zone Controller Expansion Module Components Zone Controller Expansion Module Dimensions and Components 7 Non Modular ZCAP Technical G...

Страница 8: ...is used for connecting the communica tions wiring between each Non Modular VAV Zone ControllerActuator Package and or to the MiniLink Polling Device CommLink HVAC Unit Controller or other controller...

Страница 9: ...mounting bracket nuts on the ends of the universal mounting clamp enough to slide the entire actuator and plastic enclosure assembly over the terminal unit damper shaft Rotate the enclosure base actu...

Страница 10: ...onents when mounting the controller Remove the controller from its snap track mount Mark the control enclosure base using the snap track as a template Drill pilot holes in the enclosure base and secur...

Страница 11: ...Zone Controller Expansion Module Wiring Figure 8 Zone Controller Expansion Module Wiring Fan Terminals And Or Staged Electric Heat 11 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 12: ...igure 10 Zone Controller Expansion Module Wiring Fan Terminals And Or 2 Position HW Heat Figure 9 Zone Controller Expansion Module Wiring Fan Terminals And Or Modulating Hot Water Heat 12 Non Modular...

Страница 13: ...Figure 12 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary Electric Heat Figure 11 Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 13 Non Modular Z...

Страница 14: ...munications Wiring Figure 13 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary 2 Position HW Heat Figure 14 Communication Power Wiring Diagram 14 Non Modular ZCAP Technical Guide...

Страница 15: ...Non Modular Devices Transformer Sizing Figure 15 Non Modular VAV Zone Controller Actuator Package Transformer Sizing 15 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 16: ...slave wiring inter face card and modular cable are supplied with the OE523 Round Slaved Zone Damper OE738 Slaved VAV Zone Rectangular Damper Kit and the OE282 03 Slaved VAV Zone Damper Kit These are r...

Страница 17: ...d information regarding communication wiring and connec tion for Interconnected and Networked systems please see the Orion System Installation Troubleshooting Guide Power Wiring One of the most import...

Страница 18: ...ntroller The next step is programming the controller for your specific require ments In order to configure and program the Non Modular VAV Zone ControllerActuator Package you must have a central opera...

Страница 19: ...ional hot water valve this must be set for 0 Options available are 0 No Staging 1 1 Stage of Reheat 2 2 Stages of Reheat 3 3 Stages of Reheat Proportional Heating Signal If the box has hot water rehea...

Страница 20: ...ain fan and provide cooling or heating if so configured It will re main on until the override broadcast has not been detected for at least 2 consecutive minutes Modes of Operation There are 7 possible...

Страница 21: ...VAV Zone Controller detects that the HVAC unit is in Supply Air Heating mode indicating that the air handler has activated its heat the heating airflow minimum will be substituted for the vent minimum...

Страница 22: ...ing This prevents stages from activating at the same time Once a heating stage has been activated it must remain on for at least one minute Once it has been deactivated it must remain off for at least...

Страница 23: ...nal window starting 0 5 F below the cooling setpoint to 1 5 F above the cooling setpoint The damper airflow is never allowed to modulate outside the user adjusted minimum and the maximum setpoints The...

Страница 24: ...ng setpoints The Auxiliary Heat Relay energizes at 0 5 F below the Auxiliary Heat Setpoint and de energizes 0 5 F above the Auxiliary Heat Setpoint The Auxiliary Heat will continue to function regardl...

Страница 25: ...all amount of damper error On pressure independent terminal units the airflow is maintained to within roughly 3 of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal u...

Страница 26: ...clared Maverick by the MiniLink Polling Device The zone has been configured as a VOTING zone If all the above tests are passed the zone temperature and setpoints are then included in the HVAC Mode dec...

Страница 27: ...ime so that the VAV Zone Controllers can read it and use it in their tenant and trend logs Caution These logs are subject to loss if a power outage occurs because there is no battery backed memory on...

Страница 28: ...light up the board is probably defective STAT LED Operations As previously described when the board is first powered up the LED will do the following Flashes Once Off for 5 seconds STAT LED blinks th...

Страница 29: ...entered in the configuration screen or the airflow through the box will be incorrect If none of the aforementioned procedures solves the problem remove power from the VAV Zone Controller Shut down the...

Страница 30: ...33 4 620 5 80531 4 550 0 69822 4 474 5 60552 4 390 10 52500 4 297 15 45902 4 200 20 40147 4 095 25 35165 3 982 30 30805 3 862 35 27140 3 737 40 23874 3 605 45 21094 3 470 50 18655 3 330 52 17799 3 275...

Страница 31: ...Modular and Digital Room Sensor Testing Figure 20 Testing Resistance Voltage On Modular Digital Room Sensors 31 Non Modular ZCAP Technical Guide Troubleshooting...

Страница 32: ...Method 19 C C1 8 C2 8 C3 8 CFM Factor 19 Clockwise to Open Damper 19 Components Pressure Dependent VAV Zone Controller Actuator Package 6 Pressure Independent VAV Zone Controller Actuator Package 6 Zo...

Страница 33: ...25 Connecting to Power Comm Board 15 Modes of Operation 20 Modular Connectors Actuator 8 Power Comm 8 Modular Devices Transformer Sizing 15 Modular Room Sensor Override Button 20 Modular Service Tool...

Страница 34: ...pplications 8 Analog Output 8 Auxiliary Heat 8 Fan Enable 8 Heating Stage 1 8 Heating Stage 2 8 Relay Sequencing 8 Relay Staging 22 Resistance Testing Digital Room Sensor 31 Modular Room Sensor 31 Rev...

Страница 35: ...scribed 3 Vent Minimum 21 Voltage Testing Digital Room Sensor 31 Modular Room Sensor 31 Voting 26 Voting Zone 19 W Wiring 2 Position HW Heat 12 Auxiliary 2 Position HW Heat 14 Auxiliary Electric Heat...

Страница 36: ...NMZCAP TGD 01D Printed in the USA November 2015 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: