IMG-111 User Manual
ORing Industrial Networking Corp. 46
Auto Scan
Scan the data port automatically.
Idle Timeout
When serial port stops data transmission for a defined period of time
(Idle Timeout), the connection will be closed and the port will be freed
and try to connect with other hosts. 0 indicate disable this function.
Factory default value is 0. If Multilink is configured, only the first host
connection is effective for this setting.
Alive Check
The serial device will send TCP alive-check package in each defined
time interval (Alive Check) to remote host to check the TCP
connection. If the TCP connection is not alive, the connection will be
closed and the port will be freed.
0
indicate disable this function.
Factory default is
0
.
Max Connection
The number of maximum connections can be supported. The
maximum value is
5
, default values is
1
.
TCP Client Mode
In TCP Client Mode, device can establish a TCP connection with server by the method
you have settled (Startup or any character). After the data has been transferred, device
can disconnect automatically from the server by using the TCP alive check time or Idle
time settings.