2

3. Connection

3.1 Connecting Diagrams

Using a variable resistor

~

indicate terminal numbers for variable resistors.

Turn the knob right to increase air flow-static pressure.

Variable resistor : 200k

1/4W

with a linear resistance vs. angle curve

Using a fixed resistor

Fixed resistors that use relays or the like can also be switched.

R1+R2+R3=200k

(max.)  1/4W (min.)

3.2 Inside the terminal box

The recommended tightening torque for the terminal screws is 1.4N

m (14kgcm).

Recommended lead diameter

Power supply: AWG20 (0.5mm

2

), Ground: AWG18 (0.75mm

2

) min.

Crimp style terminals that can be used

Round terminal type with insulation

U-shaped terminal type with insulation

V1.25-4

AV1.25YS4A

(JAPAN SOLDERLESS TERMINAL MFG. CO., LTD.) 

(JAPAN SOLDERLESS TERMINAL MFG. CO., LTD.)

or other equivalent product

or other equivalent product                                

φ

4.3mm (min.)

9mm(min.)

8

m

m

(max.)

9mm(min.)

4.3mm(min.)

 

8

m

m

(max.)

1

2

Line

Ground

Blue

V.R.

Blue

Lead for connecting
variable resistor

3

1

2

1

2

Line

V.R.

Ground

Blue

R1

R2

R3

Blue

1

2

3

Lead for connecting
variable resistor

1

2

3

12

3

Ground terminal (green)

4

×

8

Terminal screws

2-M4

×

12

4. Installation

Install the fan  in locations that meet the following conditions.

Indoors (the product is designed and manufactured to be mounted in a machine.)

Ambient temperature 

10

(14°F)

〜+

60

(140°F)  (Non-freezing)

Ambient humidity 0

85%  (Non-condensing)

No explosive, flammable, and/or corrosive gas.

No exposure to direct sunlight.

No splashing of water, or exposure to dust or debris.

No oil or grease, organic solvents, acid or alkaline chemicals.

No continuous vibration or excessive shock.

Insert a noise filter when there is a big noise source.

Installation category

, Pollution degree 2, Class

equipment (EN standard).

Содержание ORIX MRS18V2

Страница 1: ...ring operation please attach the following warning label so that it is clearly visible Warning label Do not touch the fan blades when the fan is in operation The use of the optional fingerguard is recommended to ensure protection Wegen der Verletzungsgefahr dürfen die Lüfterflügel bei Ventilatorbetrieb nicht berührt werden Der Gebrauch des als Sonderzubehör erhältlichen Fingerschutzes ist empfehle...

Страница 2: ...G CO LTD or other equivalent product or other equivalent product φ4 3mm min 9mm min 8mm max 9mm min 4 3mm min 8mm max 1 2 Line Ground Blue V R Blue Lead for connecting variable resistor 3 1 2 1 2 Line V R Ground Blue R1 R2 R3 Blue 1 2 3 Lead for connecting variable resistor 1 2 3 1 2 3 Ground terminal green M4 8 Terminal screws 2 M4 12 4 Installation Install the fan in locations that meet the foll...

Страница 3: ...Circuit damage may result Example of Variable Resistor Installation 3 Variable resistor unit Lead wire Lead wire Solder wrap lead around Soldered terminal Enlargement of Circular Area Heat shrink tube two to three times 50 60 40 70 80 90 30 20 10 100 0 Variable resistor Panel Cut Out drawing Insulation sheet Mounting panel Scale plate Nut Crown washer Knob Stop screw φ3 7 5 0 4 φ10 4 1 Mounting th...

Страница 4: ...SW1 Line Circuit breaker 1 2 Fan MRS18V2 1 2 4 3 E Noise filter SW1 Line Circuit breaker Variable resistor Using a variable resistor 1 2 Fan MRS18V2 Characteristics specifications and dimensions are subject to change without notice Please contact your nearest ORIENTAL MOTOR office for further information ORIENTAL MOTOR CO LTD Headquarters Tel 03 3835 0684 Fax 03 3835 1890 ORIENTAL MOTOR EUROPA Gmb...

Отзывы: