background image

Handling the product without observing the instructions that accompany a "CAUTION" 

symbol may result in injury or property damage.

OPERATING MANUAL

Thank you for purchasing an Oriental Motor product.

This Operating Manual describes product handling procedures and safety precautions.

 Please read it thoroughly to ensure safe operation.

 Always keep the manual where it is readily available.

Thermostat for fan

 

AM2-XA1

Thermostat for heater

 

AM2-XB1

HF-3150-6

• 

Do not use the product in explosive or corrosive environments, in the presence of 

   flammable gases, locations subjected to splashing water, or near combustibles.

 Only qualified and educated personnel should be allowed to perform installation, 

   connection, operation and inspection of the product.

 Do not transport, install, connect or inspect the product while the power is supplied.

   Always turn the power off before carrying out these operations.

 Connect the product securely according to the wiring diagram.

 Do not disassemble or modify the product.

 

Refer all such internal inspections and repairs to the branch or sales office from 

   which you purchased the product.

 Do not use the product beyond its specifications.

 Use this product in combination with fans or heaters of Oriental Motor.

 Provide safety measures according to the instructions of the connected device.

 To dispose of the product, disassemble it into parts and components as much as 

   possible and dispose of individual parts/components as industrial waste.

The precautions described below are intended to ensure the safe and correct use of

the product, and to prevent the customer and others from exposure to the risk of injury.

Use the product only after carefully reading and fully understanding these instructions.

Handling the product without observing the instructions that accompany a "Warning" 

or "Caution" symbol may result in fire, electric shock, injury or equipment damage.

The temperature at which the fan turns ON

is set to 40 °C (104 °F), and the temperature 

inside the enclosure rises and the fan 

operates:

The temperature at which the heater turns

OFF is set to 10 °C (50 °F), and the 

temperature inside the enclosure drops and 

the heater operates:

WARNING

CAUTION

Safety precautions

Only qualified and educated personnel should work with the product.

Use the product correctly after thoroughly reading the section "Safety precautions".

The product described in this manual has been designed and manufactured to be

incorporated in general industrial equipment. Do not use for any other purpose.

Oriental Motor Co., Ltd. is not responsible for any damage caused through failure to 

observe this warning.

Operation flow (image)

Handling the product without observing the instructions that accompany a "WARNING" 

symbol may result in serious injury or death.

Installation

If the product does not operate normally, refer to this section, and check in the order 
of 

1

 

 

2

1. Operation of contact

Check the condition of the contact by rotating the temperature-setting dial at room 

temperature.

• 

Thermostat for fan: Turn the setting dial from "contact ON [0 °C (32 °F)]" to "contact 

   OFF [60 °C (140 °F)]". If the product is normal, the contact will be OFF.

• 

Thermostat for heater: Turn the setting dial from "contact OFF [0 °C (32 °F)]" to 

   "contact ON [60 °C (140 °F)]". If the product is normal, the contact will be ON. If the 

   contact "ON" state or contact "OFF" state is continued when the setting dial is set 

   to any of the temperature, contact your nearest Oriental Motor sales office.

2. Operating temperature

 

The temperature difference against the setting temperature of this product is ±5 °C 

(±9 °F) [when setting to 23 °C (73 °F)]. Check the setting temperature and ambient 

temperature.

Troubleshooting and remedial actions

 

Location for installation

 Indoors

 Operating ambient temperature: –35 to 

+

80 °C (–31 to 

+

176 °F) (non-freezing)

 Operating ambient humidity: 95% or less (non-condensing)

 Area that is free of explosive atmosphere or toxic gas (such as sulfuric gas) or liquid

 Area not exposed to direct sun

 Area free of excessive amount of dust, iron particles or the like

 Area not subject to splashing water (rain, water droplets), oil (oil droplets) or other 

   liquids

 Area not subject to continuous vibration or excessive shocks

 Area free of excessive electromagnetic noise (from welders, power machinery, etc.)

 Area free of radioactive materials, magnetic fields or vacuum

Mount the product to a 35 mm (1.38 in.) width DIN rail.

 

Method of installation

 Fan

 Heater

 Do not drop the product. Dropping impact may cause damage to the product.

 Do not install the product in such a way that the ventilation at the slit is blocked.

 Do not let foreign objects enter the inside of the product.

Note

Standards and CE Marking

This product is recognized by UL and certified by VDE.

This product is affixed the CE Marking under the Low Voltage Directive, 

EMC Directive, and RoHS Directive.

Overvoltage category

, Pollution degree 2, Class

equipment

For EN standards

• 

Installation conditions

Specification

Model
Oriental Motor model name
Temperature setting range
Switch temperature difference

Reset (differential)

Type of Sensor

Color

Display unit

Setting dial

ON when activated, 

OFF when recovered

OFF when activated, 

ON when recovered

0 to 

+

60 °C (32 to 

+

140 °F)

±

5 °C (

±

9 °F) [When setting to 23 °C (73 °F)]

°C

Operating temperature

 

4 °C

±

3 °C (7 °F

±

5 °F)

Thermo bimetal

AM2-XA1

AM2-XB1

Thermostat for fan 

(Normally open)

Blue

Thermostat for heater 

(Normally closed)

Red

Published in November 2021

Applicable standards

Certification

body

Oriental Motor

model name

Manufacturer: STEGO Elektrotechnik GmbH

AM2-XA1

Type STS 011

Model No. 01116.0-00

Manufacturer

model name

AM2-XB1

Type STO 011

Model No. 01115.0-00

UL 60730-1

UL 60730-2-9

CSA E60730-1

CSA E60730-2-9

EN 60730-1

EN 60730-2-9

UL

VDE

Technical Support  Tel:800-468-3982

8:30am EST to 5:00pm PST (M-F)

www.orientalmotor.com

• Please contact your nearest Oriental Motor office for further information.

Schiessstraße 44, 40549 Düsseldorf, Germany

Technical Support  Tel:00 800/22 55 66 22

www.orientalmotor.de

Unit 5 Faraday Office Park, Rankine Road, 

Basingstoke, Hampshire RG24 8QB UK

Tel:+44-1256347090

www.oriental-motor.co.uk

Tel:+33-1 47 86 97 50

www.orientalmotor.fr

Tel:+39-02-93906347

www.orientalmotor.it

4-8-1Higashiueno,Taito-ku,Tokyo 110-8536 

Japan

Tel:+81-3-6744-0361

www.orientalmotor.co.jp

Tel:400-820-6516

www.orientalmotor.com.cn

Tel:0800-060708

www.orientalmotor.com.tw

Singapore

Tel:1800-842-0280

www.orientalmotor.com.sg

Tel:1800-806-161

www.orientalmotor.com.my

Tel:1800-888-881

www.orientalmotor.co.th

Korea

Tel:080-777-2042

www.inaom.co.kr

Tel:1800-120-1995 (For English)

  1800-121-4149 (For Hindi)

www.orientalmotor.co.in

 

Copyright  ORIENTAL MOTOR CO., LTD. 2013

 Unauthorized reproduction or copying of all or part of this Operating Manual is prohibited.

 Characteristics, specifications and dimensions are subject to change without notice.

                         is registered trademarks or trademarks of Oriental Motor Co., Ltd., in 

  Japan and other countries.

20 °C

30 °C

40 °C

Fan ON

Fan OFF

Time

Operation

Operation

Time

0 °C

10 °C

20 °C

Heater OFF

Heater ON

 If connecting two or more fans (or heaters), use a terminal block for relay.

  Do not connect lead wires from multiple units directly to the thermostat.

 When using the product in the environment where the operating ambient 

   temperature is 70 °C (158 °F) or more, use a heat-resistant cable for connection.

Connection

Connect the thermostat between the fan (or heater) and power supply.

The terminals of the thermostat are the solderless type. Connect using the solid wire 

or rod terminal.

Applicable wire: 
   AWG18 to 13 (0.75 to 2.5 mm

2

)

Strip Length

   5 mm (0.2 in.)
Screw-tightening torque of terminal block:

 1 N∙m (142 oz-in) or less

Power

supply

Fan or heater

1st

2nd

Reset

4 °C

Reset

4 °C

Отзывы: