TECHNICAL DATA
3.
PROFIBUS INTERFACE
Připojení:
screw-in terminals
Standard interface
EIA RS-485
Interface protocol
ProfiBus-DP
Recommend. cable
shielded twisted double-line
characteristic resistance: 135...165 Ω
cable capacity: < 30 pF/m
conductor cross section: > 0,32 mm
2
loop resistance (2 wires): < 110 Ω/km
Transmission rate
9.6 kBit/s až 12 000 kBit/s
Max. cable length
1 200 m at baud rate 9.6 / 19.2 / 93.75 kBit/s
1 000 m at baud rate 187.5 kBit/s
400 m at baud rate 500 kBit/s
200 m at baud rate 1 500 kBit/s
100 m at baud rate 3 000/6 000/12 000 kBit/s
Flexible connection
permitted up to transmission rate of max. 1 500
kBit/s, for security purposes should not be used
for transmission rates higher than 500 kBit/s
Insulation resistance
for pollution degree II, meas.category III.
> 300 V (ZI), 150 V (DI)
Status projection
3 LED (on the communication card)
No. of participants in one network segment (master/slave): max. 32
No. of participants when repeaters used: max. 126
INTERNAL COMMUNICATION
Baud rate
600 Bit/s to 115 200 Bit/s (default 9600)
How often
0,1s to 17s + communication time according to Baud
rate (default 0,6s)
PROFINET INTERFACE
Connection
2x RJ45, isolated
Interface protocol
ProfiNet
Transmission rate
100 MBit / s
Insulation resistance
for pollution degree II, meas.category III.
> 300 V (ZI), 150 V (DI)