![Orbit Merret OM 351 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/orbit-merret/om-351/om-351_manual_1648155060.webp)
60
|
INSTRUCTIONS FOR USE
OM 351
INPUT
selectable in confi guration menu
DC
DC 1
±2 mA
< 200 mV
Input 1
±20 mA
< 200 mV
Input 1
±200 mV
100 kOhm
Input 2
±2 V
100 kOhm
Input 2
±20 V
10 MOhm
Input 3
±200 V
10 MOhm
Input 3
DC 2
±1 A
< 150 mV
Input 1
±5 A
< 150 mV
Input 1
±60 mV
100 kOhm
Input 2
±150 mV
100 kOhm
Input 2
range is fi xed, as per order
AC
Range U:
0...10 V
100 kOhm
Input 2
0...120 V
10 MOhm
Input 3
0...250 V
10 MOhm
Input 2
0...450 V
10 MOhm
Input 3
Range I:
0...60 mV
100 kOhm
Input 1
0...150 mV
100 kOhm
Input 1
0...300 mV
100 kOhm
Input 1
0...1 A
< 150 mV
Input 1
0...5 A
< 150 mV
Input 1
selectable in confi guration menu
PM
0/4...20 mA
< 400 mV
Input 1
0...2 V
1 MOhm
Input 2
0...5 V
1 MOhm
Input 3
0...10 V
1 MOhm
Input 3
range is fi xed, as per order
OHM
0...200
Ohm
0...2 kOhm
0...20
kOhm
0...100
kOhm
5...105
Ohm
Connection:
2, 3 or 4-wire
RTD
Pt xxxx
-50,0°...199,9°C/-50,0°...400°C
Ni xxxx
-30,0°...199,9°C
Type Pt:
100/500/1 000 Ohm, platinum couple
s
α
=0,00385Ohm/Ohm/°C
Type Ni:
Ni 1 000, 5000 ppm/6180 ppm
Connection:
2, 3 or 4-wire
selectable in confi guration menu
T/C
Type: J
(Fe-CuNi)
-200°...900°C
K (NiCr-Ni)
-200°...1 300°C
T
(Cu-CuNi)
-200°...400°C
E
(NiCr-CuNi)
-200°...690°C
B (PtRh30-PtRh6) 300°...1 820°C
S (PtRh10-Pt)
-50°...1 760°C
R (Pt13Rh-Pt)
-50°...1 740°C
N (Omegalloy)
-200°...1 300°C
DU
Lin. pot.supply
2,5 VDC/6 mA
min. potentiometer resistance is 500 Ohm
PROJECTION
Display:
1999, intensive red or green 7-segment LED,
digit height 14 mm
Projection: ±1999
Decimal point:
adjustable - in programming mode
Brightness:
adjustable - in programming mode
INSTRUMENT ACCURACY
Temperature coef.: 100 ppm/°C
Accuracy:
±0,2% of the range + 1 digit
±0,3 % of the range + 1 digit
T/C, AC
Resolution: 0,1°/1°C
R T D
1°C
T/C
Rate:
0,5 - 1,2 - 2,5 - 5 - 10 maeasurements/s
Overload capacity: 10x (t < 100 ms), 2x (long-term)
Digital fi lter
adjustable in confi guration menu
Comp.of conduct:
max. 40 Ohm
RTD
Comp.of cold junct.: adjustable
T / C
0°...60°C or automatic
Functions:
Tare - display resetting
Hold - stop measuring (upon contact)
Lock - control keys locking
OM Link:
Company communication interface for instrument opera-
tion, setting and update
Watch-dog:
reset after 25 ms
Calibration:
at 25°C and 40 % r.h.
COMPARATOR
Type:
digital, adjustable in the menu
Limits: ±1999
Hysteresis:
0…999
Delay: 0…99,9
s
Outputs:
2x relays with switch-on contact (Form A)
(230 VAC/30 VDC, 3 A)*
Relay:
1/8 HP 277 VAC, 1/10 HP 125 V, Pilot Duty D300
* values apply for resistance load
TECHNICAL DATA
11
Содержание OM 351
Страница 25: ...INSTRUCTIONS FOR USE OM 351 25 RTD RTD RTD RTD RTD RTD RTD RTD RTD RTD 5 SETTING light light ...
Страница 27: ...INSTRUCTIONS FOR USE OM 351 27 T C T C T C T C T C T C T C T C T C T C T C 5 SETTING light light ...
Страница 33: ...INSTRUCTIONS FOR USE OM 351 33 5 SETTING light light ...
Страница 35: ...INSTRUCTIONS FOR USE OM 351 35 6 SETTING profi profi ...
Страница 53: ...INSTRUCTIONS FOR USE OM 351 53 6 SETTING profi profi ...
Страница 55: ...INSTRUCTIONS FOR USE OM 351 55 SETTING user user 7 ...
Страница 59: ...INSTRUCTIONS FOR USE OM 351 59 ...