Airflow Precautions
Related Information
■
“Physical Specifications” on page 17
■
“Electrical Specifications” on page 18
■
“Input Power Information” on page 19
■
“DC Power Source, Power Connection, and Grounding Requirements” on page 21
■
“Overcurrent Protection Requirements” on page 20
■
“Environmental Requirements” on page 22
■
“Airflow Precautions” on page 24
Airflow Precautions
Caution -
Proper airflow is essential for keeping the server's internal temperatures within a safe
operating range.
Air flows from the front to the rear of the server.
Follow these guidelines to ensure unrestricted airflow in the server:
■
Adhere to the minimum airflow clearance specifications. See
■
Install the server so the front faces the cool aisle and the rear faces the warm aisle.
■
Do not direct warm air into the server.
■
Prevent recirculation of air within a rack or cabinet.
■
When servicing server internal components, ensure that air ducts, baffles, and filler panels
are properly installed.
■
Route cables so they do not interfere with airflow.
24
Netra SPARC S7-2 Server Installation Guide • January 2017
Содержание Netra SPARC S7-2
Страница 1: ...Netra SPARC S7 2 Server Installation Guide Part No E73206 03 January 2017 ...
Страница 2: ......
Страница 8: ...8 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Страница 10: ...10 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Страница 26: ...26 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Страница 60: ...60 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Страница 96: ...96 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Страница 102: ...102 Netra SPARC S7 2 Server Installation Guide January 2017 ...