Table 1-30 (Cont.) Low-voltage 24 kVA Three Phase PDUs for North America,
South America, Japan and Taiwan (2 PDUs per Rack)
Option
Requirement, per PDU
Outlets
42 x C13; 6 x C19
Outlet groups
6
Group protection (UL489 2-pole circuit
breaker)
20A
Data center receptacle
IEC309-3P4W-IP67 60A 250VAC 3ph
(Hubbell equivalent is HBL460R9W)
The following are needed to connect an Oracle Exadata system to a low-voltage three-
phase power source:
•
4 power cords for two PDUs
•
4 receptacles to connect the PDUs
(page 1-41) lists the PDU requirements for high-voltage 24 kVA three
phase PDUs. The following specifications are per PDU.
Table 1-31 High-voltage 24 kVA Three Phase PDUs for Europe, the Middle East
and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan (2
PDUs per Rack)
Option
Requirement, per PDU
Voltage
220/380 - 240/415 VAC 3-phase
Frequency
50/60 Hz
Current
18.1 A maximum per phase
Power rating
25 kVA
Output current
108.6A (6 x 18.1 A)
Outlets
42 x C13; 6 x C19
Outlet groups
6
Group protection (UL489 1-pole circuit
breaker)
20A
Data center receptacle
IEC309-4P5W-IP44 32A 400VAC 3ph
(Hubbell equivalent is HBL532R6W)
The following are needed to connect an Oracle Exadata system to a high-voltage
three-phase power source:
•
4 power cords for two PDUs
•
4 receptacles to connect the PDUs
(page 1-42) lists the requirements for 37 kVA low-voltage three-phase
PDUs for Oracle Exadata Database Machine X6-8, X5-8, and X4-8 with more than four
database servers. There are two PDUs per rack. The following specifications are per
PDU.