(page 1-38) lists the requirements for 15 kVA high-voltage three-phase
PDUs for Europe, the Middle East, Africa, and Asia Pacific, except Japan and Taiwan.
There are two PDUs per rack. The following specifications are per PDU.
Table 1-27 High-voltage 15 kVA Three Phase for Europe, the Middle East and
Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan (2 PDUs
per Rack)
Option
Requirement, per PDU
Voltage
220/380 - 240/415 VAC 3-phase
Frequency
50/60 Hz
Current
25 A maximum per phase
Power rating
14.4 kVA
Output current
62.7 A (3 x 20.9 A)
Outlets
42 x C13; 6 x C19
Outlet groups
6
Group protection (UL489 1-pole circuit
breaker)
20A
Data center receptacle
15kVA, three phase, 5-pin, IEC 60309 32A, 5-
pin 230/400V, three phase IP44
The following are needed to connect an Oracle Exadata system to a high-voltage
three-phase power source:
•
2 power cords for two PDUs, 25 amperes at 220/380 - 240/415 VAC three-phase
•
2 receptacles to connect the PDUs to 2 IEC 60309 32A 5-pin 230/400VAC 3ph
IP44 data center receptacles
(page 1-38) shows the high-voltage three phase PDU power connector for
EMEA, and APAC, except for Japan and Taiwan.
Figure 1-4 High-voltage Three Phase Power Connector
(page 1-39) lists the requirements for low-voltage 22 kVA single phase
PDUs for North America, South America, Japan, and Taiwan. There are two PDUs per
rack. The following specifications are per PDU.
Chapter 1
Electrical Power Requirements
1-38