1.1.12 General Environmental Requirements for Oracle Exadata
Storage Expansion Rack X6-2 and later
For Oracle Exadata Storage Expansion Rack X6-2 and more recent systems, to get
the environmental requirements, such as weight, acoustic level, power, cooling, and
air flow, use the Oracle Exadata Configuration Assistant, available on Oracle
Technology Network:
Oracle Exadata Configuration Assistant (OECA) Downloads
1.1.13 General Environmental Requirements for Oracle Exadata
Storage Expansion Rack X5-2
The environmental requirements for Oracle Exadata Storage Expansion Rack X5-2
depend on the size of the system.
(page 1-20) shows the general
environmental requirements for each type of Oracle Exadata Storage Expansion Rack
X5-2.
Table 1-11 Environmental Requirements for Oracle Exadata Storage Expansion
Rack X5-2
Environmental
Component
Oracle Exadata
Storage Expansion
X5-2 Full Rack
Oracle Exadata
Storage Expansion
X5-2 Half Rack
Oracle Exadata
Storage Expansion
X5-2 Quarter Rack
Weight
•
Extreme Flash
drives: 821 kg
(1810 lbs)
•
High capacity
drives: 915.8 kg
(2019 lbs)
•
Extreme Flash
drives: 546.6 kg
(1205 lbs)
•
High capacity
drives: 591.5 kg
(1304 lbs)
•
Extreme Flash
drives: 364.5 kg
(804 lbs)
•
High capacity
drives: 384.4 kg
(848 lbs)
Acoustic levels
82 db(A)
79 db(A)
76 db(A)
Power
•
Extreme Flash
drives
Maximum: 13.1
kVA
Typical: 9.2 kVA
(varies based on
application load)
•
High capacity
drives
Maximum: 12.8
kVA
Typical: 8.9 kVA
(varies based on
application load)
•
Extreme Flash
drives
Maximum: 5.9
kVA
Typical: 4.2 kVA
(varies based on
application load)
•
High capacity
drives
Maximum: 6.9
kVA
Typical: 4.8 kVA
(varies based on
application load)
•
Extreme Flash
drives
Maximum: 3.7
kVA
Typical: 2.6 kVA
(varies based on
application load)
•
High capacity
drives
Maximum: 3.7
kVA
Typical: 2.6 kVA
(varies based on
application load)
Chapter 1
General Environmental Requirements
1-20