![Oracle EXADATA X5-2 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/oracle/exadata-x5-2/exadata-x5-2_installation-and-configuration-manual_1646081028.webp)
1.1.9 General Environmental Requirements for Oracle Exadata
Database Machine X3-8 Full Rack with Exadata Storage Server X3-2
Servers
(page 1-16) shows the general environmental requirements for Oracle
Exadata Database Machine X3-8 Full Rack with Exadata Storage Server X3-2
Servers. The other sections in this chapter provide detailed information.
Table 1-8 Environmental Requirements for Oracle Exadata Database Machine
X3-8 Full Rack with Exadata Storage Server X3-2 Servers
Environmental Component
Oracle Exadata Database Machine X3-8
Full Rack with Exadata Storage Server
X3-2 Servers
Weight
See Also: "
(page 1-34)"
929.9 kg (2050 lbs)
Acoustic levels
84 db(A)
Power
See Also: "
(page 1-34)"
•
High performance drives
Maximum: 15.3 kVA
Typical: 10.7 kVA (varies based on
application load)
•
High capacity drives
Maximum: 14.3 kVA
Typical: 10.0 kVA (varies based on
application load)
Cooling
See Also: "
(page 1-44)", and "
(page 1-45)"
•
High performance drives
Maximum: 51,200 BTU/hour (54,000 kJ/
hour)
Typical: 35,900 BTU/hour (37,900 kJ/
hour)
•
High capacity drives
Maximum: 47,800 BTU/hour (50,400 kJ/
hour)
Typical: 33,500 BTU/hour (35,300 kJ/
hour)
Air flow front-to-back (subject to actual data
center environment)
See Also: "
(page 1-44)", and "
(page 1-45)"
•
High performance drives
Maximum: Approximately 2,400 CFM
Typical: Approximately 1,700 CFM
•
High capacity drives
Maximum: Approximately 2,200 CFM
Typical: Approximately 1,550 CFM
IP Addresses
See Also: "
Address Requirements for Oracle Exadata
Database Machine
45 for Ethernet network, assuming single
cluster
22 for InfiniBand network
Chapter 1
General Environmental Requirements
1-16