![Oracle EXADATA X5-2 Скачать руководство пользователя страница 243](http://html1.mh-extra.com/html/oracle/exadata-x5-2/exadata-x5-2_installation-and-configuration-manual_1646081243.webp)
Table 5-21 Threshold Values for Oracle Exadata Database Machine X3-2
Quarter Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
10
13
A
Module 1, phase
2
0
5
6
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
5
6
B
Module 1, phase
3
0
10
13
(page 5-31) lists the threshold values for Oracle Exadata Database
Machine X3-2 Quarter Rack using a three-phase, low-voltage PDU.
Table 5-22 Threshold Values for Oracle Exadata Database Machine X3-2
Quarter Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
11
14
A and B
Module 1, phase
2
0
10
13
A and B
Module 1, phase
3
0
4
6
(page 5-31) lists the threshold values for Oracle Exadata Database
Machine X3-2 Quarter Rack using a single-phase, high-voltage PDU.
Table 5-23 Threshold Values for Oracle Exadata Database Machine X3-2
Quarter Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
9
11
A
Module 1, phase
2
0
4
6
A
Module 1, phase
3
0
0
0
Chapter 5
Configuring the Power Distribution Units
5-31