OPW 1-3100 Series Spill Container
Page 30
OPERATION INSTRUCTIONS:
Step 1:
(See Figure 2)
Attach vacuum pump to gauge assembly using the
Quick Connect Fitting.
Figure 2
Step 2:
(See Figure 3)
Make sure Test Valve is clean.
Connect Test Adaptor to Test Valve on OPW 1-3100
Series Double Wall Spill Container.
Step 3:
(See Figure 2)
Make sure that the ball valve on the DW-VAC-TEST
is open and use the pump to increase the vacuum to
-15 inches of water column as displayed on vacuum
gauge.
Step 4:
Close ball valve when -15 inches of water column is
displayed on the vacuum gauge. Allow spill
container to sit for 30 seconds. Refill spill container
to -15 inches of water column.
Step 5:
Leave the spill container undisturbed for 5 minutes
while under vacuum.
Step 6:
Check vacuum gauge after 5 minutes. If gauge
does not show 12 or more inches of water column,
the spill container has failed the test.
Figure 3
NOTE:
Keep the temperature of the unit constant
during testing. Fluctuations in temperature of the
unit could result in bias results.