IF-722ETH version 5.0.001 

IP Audio interface 

 2 inputs / 2 outputs 

IF-722ETH 

R+D Department 

3.1.

 

IP Connection, communication and control module 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground connection 

1)

 

FUSE. 

2.5 A Secondary power supply fuse. 

2)

 

POWER SUPPLY 2

 

3)

24 VDC Secondary power input. 

 

GND Contact 

4)

 

FAIL 

Contacts

 

5)

Output relay used to indicate a system failure. 
If  the  COM  contact  is  linked  to  the  NO  contact,  it 
indicates  that  there  are  no  faults  or  alarms  in  the 
system.  If  on  the  other  hand,  COM  is  linked  to  NC,  it 
indicates  that  the  equipment  is  switched  off  or  that 
alarms were detected (figure 4). 

Maximum

 DC charge current: 150 mA 

Maximum DC or AC peak charge voltage: 350 V 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

BUS

 CAN Contacts 

6)

Data  communication  bus  between  the  IF-722ETH  and 
the system peripherals (MD-30C, ME-200C, NS-CAN). 

 

OUTPUT CT Contacts

 

7)

Incorporates  three  output  contacts  configured  as  dry 
contacts. Each contact has two terminals (A and B).  
The  functionality  and  stand-by  state  (NC/NO)  are 
configured through the 

Call Point

 software. They may be 

configured  as  general  purpose  contacts  or  in  the 
evacuation  system  as  fault  notification  contacts, 

Emergency Mode

 indicator activated... 

 

INPUT Contacts CT 1, 2 and 3

 

8)

Incorporates three input contacts. 
The  functionality  and  stand-by  state  (NC/NO)  are 
configured through the 

Call Point

 software. They may be 

configured  as  general  purpose  contacts  or  in  the 
evacuation  system  as  emergency  mode  activation 
contacts, evacuation

 

message activated... 

The  detection  time  of  the  activation  pulse  of  the  input 
contacts is configurable  through the 

Call Point

 software 

(0-50-100-200-300-400-500-1000-1500-2000 
milliseconds). 
If  you  wish,  the  system  may  monitor  these  contacts 
(short-circuit or open line detection). 

 

ETH B Connector 

9)

Is  used  in  a  redundant  network  as  a  secondary 
connection to the IP network.

 

 

ETH A Connector 

10)

Is used to connect the unit to the IP network. 

 

LINK/ACTIVITY indicator

 (green LED): 

11)

When  illuminated  it  indicates  a  network  connection. 
When  flashing  it  indicates  that  data  is  being  sent  or 
received. 

 

SPEED indicator

 (yellow LED): 

12)

Speed of the network. If the LED is lit, indicates a speed 
of  100  Mbps.  If  unlit,  indicates  a  network  speed  of  10 
Mbps  (it  is  highly  recommended  to  use  a  transmission 
speed of 100 Mbps). 

 

 

No alarms  

COMPACT is turned off 

or alarms detected 

Figure 4 

FAIL RELAY STATUS 

Figure 3 

Содержание IF-722ETH

Страница 1: ...9I330A 07 10 2020 V3 2 000...

Страница 2: ......

Страница 3: ...0 9I330A 07 10 2020 V5 0 001...

Страница 4: ......

Страница 5: ...n 12 5 3 1 Speakers line connection without surveillance 12 5 3 2 Speakers line connection with surveillance 13 5 4 Input contacts 13 5 5 Output contacts 14 5 6 BUS CAN connection 14 5 7 Front USB con...

Страница 6: ...impedance high impedance or line in good condition Monitoring of the condition of the amplifier by analysing the audio signal to detect if the power stage has entered into protection mode or is turned...

Страница 7: ...deactivating the acoustic alarm in SYSTEM FAULT errors 7 CONSOLE connector Mini USB connector Allows monitoring the system Only specialised personnel 8 Front USB for inputting music 3 REAR VIEW 100 2...

Страница 8: ...n system as fault notification contacts Emergency Mode indicator activated INPUT Contacts CT 1 2 and 3 8 Incorporates three input contacts The functionality and stand by state NC NO are configured thr...

Страница 9: ...inputs configured as a paging incorporate a talk priority usage The sensitivity of the input may be modified via the software Call Point configuration AUX H 0 dB or AUX L 20 dB Also each input has a...

Страница 10: ...1 AUDIO H HOT output signal Pin 2 AUDIO C COLD output signal Pin 3 24 VDC input to monitoring the amplifier Pin 4 Not used Pin 5 Not used Pin 6 PRIORITY output contact Open collector output Pin 7 Not...

Страница 11: ...r long periods remove the battery Remove leaking batteries from the device immediately If battery acid leaks out it is essential to avoid contact with the skin eyes and mucous membranes If the acid do...

Страница 12: ...2 inputs 2 outputs IF 722ETH R D Department Unscrew and pull out the battery compartment 2 Insert the battery respecting the polarity 3 indicated in the attached figure Insert and screw the battery 4...

Страница 13: ...he equipment to the mains by means of the supplied cable and if required by safety standards a secondary power supply input of 24 VDC 5 2 Audio inputs Use the INPUT A and INPUT B connectors to connect...

Страница 14: ...or announcements Pin 1 AUDIO H HOT signal Pin 2 GND If the audio is balanced AUDIO C COLD signal Pin 3 ACK Acknowledge contact This output contact allows synchronisation with external microphone desks...

Страница 15: ...llance 5 4 Input contacts The IF 722ETH incorporates three input contacts INPUT CT 1 2 and 3 If you wish the system may monitor these contacts short circuit or open line detection ZONE 1 AMPLIFIER ZON...

Страница 16: ...24 cable 5 7 Front USB connector Playing music from an external memory The unit has a USB 2 0 port on the front panel for use as a musical program input To do this connect to this port an external mem...

Страница 17: ...e IP address for the unit and press INTRO By default the IP address is 10 1 1 1 Warning The range of IP addresses for the unit and the PC must match Otherwise the network settings of the PC must be ch...

Страница 18: ...unit receives one or several alarms from the system or when an alarm is generated by the unit itself SYSTEM FAULT indicator light Front yellow LED Illuminates when the equipment detects an internal er...

Страница 19: ...2 Audio outputs See table III Internal SD memory 16 GB Power supply 100 240 VCA primary power supply 24 VDC secondary power supply Consumption 150 mA 230 Vac 1 5 A 24 VDC Weight 5 6 Kg Finishes RAL900...

Страница 20: ...ing from a local IP microphone to a local COMPACT matrix point to point communication UDP Multicast for the audio broadcasting from a global IP microphone to the COMPACT matrixes point to multipoint c...

Страница 21: ...from PC Integration XML TCP Unicast 27000 Integration to PC optional Integration JSON TCP Unicast 28000 Direct integration and control to equipment Integration SNMP UDP Unicast 161 162 TRAPS Integrati...

Страница 22: ...705 6kbps for each audio channel RTP G 711 LAW 8KHz 8 bits 64kbps for each audio channel RTP G 711 A LAW 8KHz 8 bits 64kbps for each audio channel Note Control without alarms number of simultaneous ch...

Страница 23: ...described in this user manual are valid for software and firmware versions that are the same or later versions of IF 722ETH Firmware Application version 5 0 8619 Linux version 2 6 35 14 Input module f...

Страница 24: ...t System network specifications 10 Software and firmware versions R D Department 3 2 001 November 2018 3 1 IP Connection communication and control module FAIL contacts 5 6 BUS CAN Connection R D Depar...

Страница 25: ...use of the equipment including lack of maintenance 5 The guarantee shall not be valid whenever the following is observed Amendments or corrections made to the details of the guarantee certificate or p...

Страница 26: ...9I330A 07 10 2020 V5 0 001...

Страница 27: ...0 9I330A 07 10 2020 V5 0 001...

Страница 28: ......

Страница 29: ...sin supervisi n de l nea de altavoces 12 5 3 2 Conexi n con supervisi n de l nea de altavoces 13 5 4 Contactos de entrada 13 5 5 Contactos de salida 14 5 6 Conexi n del BUS CAN 14 5 7 Conector USB fr...

Страница 30: ...impedancia o l nea en correcto estado Supervisi n del estado del amplificador analizando la se al de audio para detectar si la etapa de potencia ha entrado en protecci n o est apagada y mediante la de...

Страница 31: ...larma ac stica al producirse un fallo SYSTEM FAULT 7 Conector CONSOLE Conector mini USB Permite monitorizar el sistema S lo personal especializado 8 USB frontal para entrada musical 3 VISTA POSTERIOR...

Страница 32: ...de fa llo indicador de Modo Emergencia activado Contactos INPUT CT 1 2 y 3 8 El equipo dispone de tres contactos de entrada La funcionalidad y el estado de reposo NC NO se confi guran a trav s del so...

Страница 33: ...entrada de avisos Las entradas configuradas como avisos disponen de prioridad de palabra El software permite tambi n el ajuste de la sensibilidad de entrada AUX H 0 dB o AUX L 20 dB Adem s cada entrad...

Страница 34: ...el software de megafon a RJ45 PIN OUT Pin 1 Salida de AUDIO H HOT Pin 2 Salida de AUDIO C COLD Pin 3 Entrada de 24 VCC de supervisi n de amplificador Pin 4 No utilizado Pin 5 No utilizado Pin 6 Contac...

Страница 35: ...un m dico Antes de colocar las pilas compruebe si los contactos del aparato y de las pilas est n limpios si es necesario l mpielos Coloque siempre pilas nuevas No utilice pilas recargables bater as No...

Страница 36: ...radas 2 salidas IF 722ETH R D Department Desatornille y extraiga el compartimento de la pila 2 Coloque la pila respetando la polaridad 3 indicada en el dibujo adjunto Inserte y fije el compartimento 4...

Страница 37: ...suministrado y si por normas de seguridad la instala ci n lo requiere una entrada de alimentaci n secundaria de 24 V C C 5 2 Entradas de audio Para conectar un micr fono o una fuente musical anal gic...

Страница 38: ...ono para avisos de megafon a al IF 722ETH Pin 1 Se al de AUDIO H HOT Pin 2 GND Si la se al es balanceada se al de AUDIO C COLD Pin 3 Contacto ACK Acknowledge Permite la sincronizaci n con pupitres ext...

Страница 39: ...actos de entrada El equipo dispone de tres contactos de entrada INPUT CT 1 2 y 3 Si se desea el sistema puede supervisar estos contactos detecci n de cortocircuito o l nea abierta AMPLIFICADOR ZONA 1...

Страница 40: ...n de m sica desde una memoria externa El equipo dispone de un puerto USB 2 0 en el panel frontal para utilizarse como entrada de programa musical Para ello conecte a este puerto una memoria externa q...

Страница 41: ...or introduzca la direcci n IP del equipo y pulse INTRO Por defecto la direcci n IP es 10 1 1 1 Atenci n El rango de direccio nes IP del equipo y las del PC deben coincidir Si no es as debe cambiar pre...

Страница 42: ...al Se enciende cuando el equipo recibe una o varias alarmas del siste ma o al generar l mismo una alarma Indicador luminoso SYSTEM FAULT Led amarillo frontal Se enciende cuando detecta un error intern...

Страница 43: ...ajes pregrabados 16 GB Alimentaci n 100 240 V c a alimentaci n primaria 24 VCC alimentaci n secundaria Consumo 150 mA 230 Vca 1 5 A 24 VCC Peso 5 6 Kg Acabados Hierro pintado negro RAL9005 Medidas 482...

Страница 44: ...cr fono IP local y la matriz COMPACT Local comunicaci n punto a punto UDP Multicast para el env o de audio desde un micr fono IP global hacia las distintas matrices COMPACT comunicaci n punto multipun...

Страница 45: ...01 Configuraciones desde el PC Integraci n XML TCP Unicast 27000 Integraci n a los PC opcional Integraci n JSON TCP Unicast 28000 Integraci n directa y control a equipos Integraci n SNMP UDP Unicast 1...

Страница 46: ...Hz 16 bits 705 6kbps por cada canal de audio RTP G 711 LAW 8KHz 8 bits 64kbps por cada canal de audio RTP G 711 A LAW 8KHz 8 bits 64kbps por cada canal de audio Nota Control sin alarmas n mero de cana...

Страница 47: ...itas en este manual de usuario son v lidas para versiones de software y firmware iguales o superiores a Firmware IF 722ETH Application version 5 0 8619 Linux version 2 6 35 14 Firmware del m dulo de e...

Страница 48: ...red en sistema Compact 10 Versiones de software y firmware R D Department 3 2 001 Noviembre 2018 3 1 M dulo de conexi n IP comunicaci n y control contactos FAIL 5 6 Conexi n del BUS CAN R D Departmen...

Страница 49: ...Los da os personales o a la propiedad que pudieran causar el uso indebido del equipo incluyendo la falta de mantenimiento 5 La garant a carecer de validez cuando se observe Enmiendas o tachaduras en...

Страница 50: ...9I330A 07 10 2020 V5 0 001...

Отзывы: